|
Posted by ronaldo123 on January 6, 2008, 3:38 pm
Hi all,
I have problem at home. Recently my oven, water heater, dryer....
stopped working. I tried playing with the breakers but it all seems
to be fine. One curious thing in the panel is that if I measure the
voltage between the 2 hot wires it reads 58volts... if I measure each
of the hot wires to the ground it measures 110volts.. is this normal?
Should the voltage between the 2 hotwires measure 220V ?
Thanks!
|