Electric water heater - repalced everything still no hot water

Home Repair - - If it ain't broken, don't fix it. Otherwise look here. 

Bookmark this page:  YahooMyWeb Yahoo!  Google Google  Windows Live Favorites Windows Live  del.icio.us del.icio.us  digg digg  Add to Netscape Netscape
Subject Author Date
Electric water heater - repalced everything still no hot water Mark 09-18-2006
If you were  Registered and logged in, you could reply and use other advanced thread options
Posted by Mark on September 18, 2006, 9:56 pm
Hi everyone. I hope someone can helo me with this as I am baffled
beyond imagination here. I have an electric hot water heater that
burned out the bottom element. I opted to replace both elements and
thermostats since this was an in-expensive investment.

So replaced both upper and lower elements, upper and lower
thermostats..and still no hot water.

one thing I did do is buy another set of elements and when I removed
the first set, I noticed that only the edges were getting hot and not
the entire element..could it be the I need to adjust the thermostat to
a higher temp?

Also, I checked all electrical wiring and I have voltage everywhere its
suppse to be.. Also did a resistance test on all 4 elements, first set
and second, and all pass with flying colors..

So I am confused and not sure where to look next...

This is a 240 volt system and both leads are hot..checked and verified.


Posted by Don Young on September 18, 2006, 11:26 pm

> Hi everyone. I hope someone can helo me with this as I am baffled
> beyond imagination here. I have an electric hot water heater that
> burned out the bottom element. I opted to replace both elements and
> thermostats since this was an in-expensive investment.
>
> So replaced both upper and lower elements, upper and lower
> thermostats..and still no hot water.
>
> one thing I did do is buy another set of elements and when I removed
> the first set, I noticed that only the edges were getting hot and not
> the entire element..could it be the I need to adjust the thermostat to
> a higher temp?
>
> Also, I checked all electrical wiring and I have voltage everywhere its
> suppse to be.. Also did a resistance test on all 4 elements, first set
> and second, and all pass with flying colors..
>
> So I am confused and not sure where to look next...
>
> This is a 240 volt system and both leads are hot..checked and verified.
>
Your post is a little confusing because if you have proper voltage across
the element and the element resistance is correct, there is no way it will
fail to heat.

When you say both 240 volt leads are hot, do you mean they have 240 volts
between them or that each has 120 volts to the neutral or ground? If the
latter, and the leads are connected to the heater, you can have one fuse or
breaker open.

With everything connected normally, test for 240 volts across the input
leads. If present, test for 240 volts across the element terminals. Do not
confuse yourself by making any measurements to neutral or ground.

If you have 240 volts at the input but not at the elements, one of the
thermostats is open or something is miswired. Most dual element heaters only
operate one element at the time. From cold, the upper element heats until
the upper thermostat gets hot enough to switch. The upper element then turns
off and the lower element is switched on, both actions done by the upper
thermostat. The bottom thermostat will still be cool and its contacts will
be closed. When the bottom element heats the water hot enough for the lower
thermostat to switch, it will turn off the bottom element.

Most of the heating is then done by the lower element, the upper element
only coming on when the top of the heater gets cooled down by using a lot of
hot water. It will help to understand this to know that the cold water goes
thru an internal "dip tube" and actually enters the heater at the bottom.

Your big mistake was in replacing the upper element and the thermostats
unnecessarily, but you should be able to get it going again if you
understand how it is supposed to work.

Don Young



Posted by George on September 19, 2006, 8:25 am

Mark wrote:
> Hi everyone. I hope someone can helo me with this as I am baffled
> beyond imagination here. I have an electric hot water heater that
> burned out the bottom element. I opted to replace both elements and
> thermostats since this was an in-expensive investment.
>
> So replaced both upper and lower elements, upper and lower
> thermostats..and still no hot water.
>
> one thing I did do is buy another set of elements and when I removed
> the first set, I noticed that only the edges were getting hot and not
> the entire element..could it be the I need to adjust the thermostat to
> a higher temp?
>
> Also, I checked all electrical wiring and I have voltage everywhere its
> suppse to be.. Also did a resistance test on all 4 elements, first set
> and second, and all pass with flying colors..
>
> So I am confused and not sure where to look next...
>
> This is a 240 volt system and both leads are hot..checked and verified.

Maybe the "dip tube" that is on the inlet side is broken or corroded
away, if that happens then the cold water comes in the top and goes
right back out the top without heating. Check to see if you have hot
water at the bottom of the tank by opening the drain valve.

George


Posted by on September 19, 2006, 9:05 am
I'm with Don on this one. If you have 240V measured across the heating
element and the heating element is good per resistance check, then it
has to heat. At least at that point in time. Keep in mind some
heaters are on a timer system controlled by the electric meter, where
power is only provided off peak at a reduced rate.

I also agree with the advice that it was a mistake to replace the
working element and 2 thermostats. In my experience, the element
failure doesn't appear to depend much on length of service. And I've
never had a thermostat go.


Posted by tony on September 19, 2006, 4:06 pm
The lower thermostat on mine stuck with the contacts closed. It kept heating
until the safety overheat breaker popped. I had to reset it after I changed
the thermostat. But I knew it had to be reset because I had no voltage on
either element. I am also mystified by the OP posting.
> I'm with Don on this one. If you have 240V measured across the heating
> element and the heating element is good per resistance check, then it
> has to heat. At least at that point in time. Keep in mind some
> heaters are on a timer system controlled by the electric meter, where
> power is only provided off peak at a reduced rate.
>
> I also agree with the advice that it was a mistake to replace the
> working element and 2 thermostats. In my experience, the element
> failure doesn't appear to depend much on length of service. And I've
> never had a thermostat go.
>



Similar ThreadsPosted
Electric Water Heater Grounded to Copper Water Pipes? October 29, 2005, 6:04 pm
Re: Electric water heater - not enough hot water January 5, 2009, 2:21 pm
Electric water heater - not enough hot water January 5, 2009, 2:17 pm
Hot Water Heater: Gas vs. Electric April 14, 2006, 8:46 am
Electric Hot Water Heater November 20, 2006, 8:59 pm
Has anyone taken apart an Electric Water Heater? March 22, 2007, 10:49 am
Water too Hot, Now Just Lukewarm (Electric Heater) October 8, 2005, 2:39 pm
Recommendation for an electric hot water heater? January 31, 2006, 8:31 pm
Replacing a water heater (electric) March 17, 2006, 8:09 am
wiring for electric water heater May 9, 2006, 2:32 am

Contact Us | Privacy Policy

XML SitemapXML Sitemap