Electrical code question

Home Repair - - If it ain't broken, don't fix it. Otherwise look here. 

Page 1 of 2       1 2 > last >> Bookmark this page:  YahooMyWeb Yahoo!  Google Google  Windows Live Favorites Windows Live  del.icio.us del.icio.us  digg digg  Add to Netscape Netscape
Subject Author Date
Electrical code question jmagerl 09-01-2007
If you were  Registered and logged in, you could reply and use other advanced thread options
Posted by jmagerl on September 1, 2007, 2:23 pm
I live in a house that used to belong to a DIY'er. Problem is, there isn't
anything he did right. I am in the middle of fixing his mess in the garage.
HEre is the situation: The main breaker is in the basement .it is a 20 Amp
dual breaker. THere is a subpanel in an upstairs closet (don't ask me why)
with 2 20 Amp fuses. One of the fuses runs to the garage. The garage is
mixed 14guage and 12 guage wiring. The other fuse runs to the family room
where hot and neutral appear to be reversed.

For now I'm doing the garage. First thing: install GFI, Second thing:
simplify the rats nest of wiring (the box going to the door opener has 8
pieces of 12 guage romex going to it),

My question: to resolve the mixed guage issue: Can I just replace the fuse
in the sub panel with a 15 amp fuse? and leave the 20 Amp breaker in the
panel. All that is in the garage is the opener, 2 outlets and 2 lightbulbs.

why would there be a ganged breaker for this circuit? I can only think of a
shared neutral unless one leg goes to the garage and the other goes to the
family room or the guy was a complete doorknob and just put it in. I
probably will get into this when I see why hot and neutral are reversed.




PexSupply Save 10 468x60
Posted by Doug Miller on September 1, 2007, 4:22 pm
>I live in a house that used to belong to a DIY'er. Problem is, there isn't
>anything he did right. I am in the middle of fixing his mess in the garage.
>HEre is the situation: The main breaker is in the basement .it is a 20 Amp
>dual breaker. THere is a subpanel in an upstairs closet (don't ask me why)

If it's a clothes closet, or linen closet, that's a Code violation.

>with 2 20 Amp fuses. One of the fuses runs to the garage. The garage is
>mixed 14guage and 12 guage wiring. The other fuse runs to the family room
>where hot and neutral appear to be reversed.
>
>For now I'm doing the garage. First thing: install GFI, Second thing:
>simplify the rats nest of wiring (the box going to the door opener has 8
>pieces of 12 guage romex going to it),
>
>My question: to resolve the mixed guage issue: Can I just replace the fuse
>in the sub panel with a 15 amp fuse?

That would resolve the Code violation inherent in having 14ga wire on a 20A
circuit. But what about the location of the subpanel?

>and leave the 20 Amp breaker in the
>panel.

Maybe -- what's the wiring between that breaker and the subpanel? If it's
14ga, that's another problem.

>All that is in the garage is the opener, 2 outlets and 2 lightbulbs.
>
>why would there be a ganged breaker for this circuit?

Because that's what you use for feeding a subpanel. Ground, neutral, and two
hots attached to a double-pole breaker.

>I can only think of a
>shared neutral unless one leg goes to the garage and the other goes to the
>family room or the guy was a complete doorknob and just put it in. I
>probably will get into this when I see why hot and neutral are reversed.

That's the only part of this arrangement that sounds normal.

--
Regards,
Doug Miller (alphageek at milmac dot com)

It's time to throw all their damned tea in the harbor again.

Posted by jmagerl on September 1, 2007, 4:59 pm

>>I live in a house that used to belong to a DIY'er. Problem is, there isn't
>>anything he did right. I am in the middle of fixing his mess in the
>>garage.
>>HEre is the situation: The main breaker is in the basement .it is a 20 Amp
>>dual breaker. THere is a subpanel in an upstairs closet (don't ask me why)
>
> If it's a clothes closet, or linen closet, that's a Code violation.

Yes its a clothes closet. Chalk another one up to the idiot. I'm not even
sure why theres a subpanel, its an attached garage. 50 ft of wire would
reach the garage from the basement panel.


arrangement that sounds normal.
>
> --
> Regards,
> Doug Miller (alphageek at milmac dot com)
>
> It's time to throw all their damned tea in the harbor again.

A different question. Thru out this whole house, He has taken the ground
wire in the romex and bent it so it was under the box termination clamp (not
sure of the nomenclature). The assumption is that the romex clamp contacts
the ground which than contacts the box by the nut. I'm having a hard time
believing that is code. In several spots he has looped the ground wire thru
a hole in the box and then nailed the box up with the intent that the ground
wire is pinched between the box and the stud. I cringe everytime I fix
something.

On several occasions I have had to explain to trades people that the house
has been sold and I am the new owner before they would come out. It seems
the idiot had a habit of asking for quotes and then asking them lots of
questions and doing it himself. The trades people had him pegged alright.



Posted by RBM on September 1, 2007, 5:21 pm
The ground wires, if more than one, should be connected together under a
crimp or wire nut and attached to the metal box by turning under a machine
screw or by using a listed green grounding clip. What he's done is incorrect



>
>>>I live in a house that used to belong to a DIY'er. Problem is, there
>>>isn't
>>>anything he did right. I am in the middle of fixing his mess in the
>>>garage.
>>>HEre is the situation: The main breaker is in the basement .it is a 20
>>>Amp
>>>dual breaker. THere is a subpanel in an upstairs closet (don't ask me
>>>why)
>>
>> If it's a clothes closet, or linen closet, that's a Code violation.
>
> Yes its a clothes closet. Chalk another one up to the idiot. I'm not even
> sure why theres a subpanel, its an attached garage. 50 ft of wire would
> reach the garage from the basement panel.
>
>
> arrangement that sounds normal.
>>
>> --
>> Regards,
>> Doug Miller (alphageek at milmac dot com)
>>
>> It's time to throw all their damned tea in the harbor again.
>
> A different question. Thru out this whole house, He has taken the ground
> wire in the romex and bent it so it was under the box termination clamp
> (not sure of the nomenclature). The assumption is that the romex clamp
> contacts the ground which than contacts the box by the nut. I'm having a
> hard time believing that is code. In several spots he has looped the
> ground wire thru a hole in the box and then nailed the box up with the
> intent that the ground wire is pinched between the box and the stud. I
> cringe everytime I fix something.
>
> On several occasions I have had to explain to trades people that the
> house has been sold and I am the new owner before they would come out. It
> seems the idiot had a habit of asking for quotes and then asking them lots
> of questions and doing it himself. The trades people had him pegged
> alright.
>



Posted by aemeijers on September 1, 2007, 7:11 pm

> The ground wires, if more than one, should be connected together under a
> crimp or wire nut and attached to the metal box by turning under a machine
> screw or by using a listed green grounding clip. What he's done is
> incorrect
>
>
Incorrect by current code, but I know it was common practice from the late
50's (when romex with the bare ground wire came into comon use) at least
until the late 70's. Given how brittle old wire gets, and how seldom there
is any usable slack in the walls, is there any good reason to try to re-wire
old work to meet current practice? All the outlets in this place were wired
that way when I changed them out, and I opted not to disturb the existing
clamps beyond giving the screws a turn to make sure the clamps were snug.
All outlets show 'green light' on the idiot meter, indicating a good ground.
Note that the outlets were not pig-tailed, they were daisy-chained via the
side screws (albeit with the polarity reversed on about half of them.)

aem sends....



Page 1 of 2       1 2 > last >>
Similar ThreadsPosted
Electrical code question... May 13, 2007, 9:52 pm
Electrical code question December 12, 2007, 11:44 am
Electrical Code Question (Canada) January 28, 2006, 4:49 pm
Electrical Code question:"accessibility" August 14, 2008, 5:39 pm
Electrical Code Question - Buried wire December 18, 2006, 8:26 pm
electrical code Q July 13, 2005, 2:50 pm
Is This The Best Electrical Code Book To Have? February 11, 2005, 1:23 am
Floating Electrical Box- Is it Code Compliant ? October 25, 2005, 8:50 am
electrical protective plate code December 15, 2007, 8:50 pm
Does electrical code care about the color of staples? December 30, 2005, 2:06 pm

Contact Us | Privacy Policy

XML SitemapXML Sitemap