Posted by Art Todesco on July 17, 2005, 12:39 pm


Thanks. BTW, it was a bit low on freon.
Also, this happened at night
where I run the blower on a slower speed
cut off a section of the house
via a motor driven duct damper. It has
been ok for some 10 or 15 years.
The other factor is that the AC was
turned on when the house was already
very hot ... so it had to run longer
than usual night time runs.

RP wrote:
>
>
> Art Todesco wrote:
>
>> I have a question for you hvac guys. Can a central AC A coil ice up
>> from reduced air flow in the condenser (40-50% of the condenser matted
>> up)? I know this can happen from low airflow in the evaporator. And
>> I know it can happen when the freon is low. If yes, can you explain
>> what happens to pressures when it happens? Thanks,
>
>
> Typically no, but it can happen, especially on window shakers. I
> suppose from the unanimity of the other responses that most techs would
> automatically assume either a solid restriction in the cap tube or
> filter, or a loss of charge as the cause. After having cleaned the thing
> up and rechecked it, and it is suddenly flying right, they naturally
> assume that the blockage has dislodged itself, problem solved. They
> might want to reconsider. Cap tubes don't typically clear themselves
> because soap and water met the outside of them :)
>
> TXV's can also go into an excessive hunting mode causing evap icing.
> Excessive flashgas doesn't help matters.
>
> I've seen both more than once, it doesn't get anymore straightforward
> than that. But it isn't exactly a common occurrence.
>
> hvacrmedic
>
>
>
>


Posted by RP on July 17, 2005, 2:52 pm




Art Todesco wrote:

> Thanks. BTW, it was a bit low on freon. Also, this happened at night
> where I run the blower on a slower speed cut off a section of the house
> via a motor driven duct damper. It has been ok for some 10 or 15 years.
> The other factor is that the AC was turned on when the house was already
> very hot ... so it had to run longer than usual night time runs.

The longer runtime, if it played any part, did nothing more than prevent
the melting that would have occurred during the off cycle. Given that it
was hotter inside, then this is that much more an incorrect assessment,
since hotter air over the evaporator would tend to counter the real
cause of the freezing.

There is no such thing as evaporator freezing due to excessive runtimes.
If there is freezing, then any excessive runtime is a symptom of the
problem and not the problem itself.

hvacrmedic

>>
>>
>> Art Todesco wrote:
>>
>>> I have a question for you hvac guys. Can a central AC A coil ice up
>>> from reduced air flow in the condenser (40-50% of the condenser
>>> matted up)? I know this can happen from low airflow in the
>>> evaporator. And I know it can happen when the freon is low. If yes,
>>> can you explain what happens to pressures when it happens? Thanks,
>>
>>
>>
>> Typically no, but it can happen, especially on window shakers. I
>> suppose from the unanimity of the other responses that most techs
>> would automatically assume either a solid restriction in the cap tube
>> or filter, or a loss of charge as the cause. After having cleaned the
>> thing up and rechecked it, and it is suddenly flying right, they
>> naturally assume that the blockage has dislodged itself, problem
>> solved. They might want to reconsider. Cap tubes don't typically clear
>> themselves because soap and water met the outside of them :)
>>
>> TXV's can also go into an excessive hunting mode causing evap icing.
>> Excessive flashgas doesn't help matters.
>>
>> I've seen both more than once, it doesn't get anymore straightforward
>> than that. But it isn't exactly a common occurrence.
>>
>> hvacrmedic
>>
>>
>>
>>



Page 2 of 2       << first < 1 2
Similar ThreadsPosted
A/C evaporator location December 10, 2005, 11:54 am
evaporator ice formation June 29, 2005, 8:02 am
New condenser, old evaporator April 17, 2007, 5:41 pm
A/C Evaporator Unit; Help Please! May 23, 2007, 4:07 pm
Evaporator coil needs replacing? April 18, 2006, 3:45 pm
A/C - Evaporator Coil Replacement July 12, 2006, 10:58 pm
add auto evaporator to window AC July 9, 2007, 2:59 pm
refrigerator evaporator fan motor August 17, 2007, 1:38 pm
New Evaporator Coils necessary for new Condenser ? May 6, 2008, 1:50 pm
GE Frige evaporator coils freezes-up January 28, 2007, 12:12 pm

Contact Us | Privacy Policy

XML SitemapXML Sitemap