Furnace pressure valve leaking. Andrew 03-02-2007
If you were  Registered and logged in, you could reply and use other advanced thread options
Posted by Charlie Morgan on March 3, 2007, 7:58 am



>The pressure overflow valve on my furnace is leaking. It's a gas
>fired hot water radiator system. I recently replaced the corroded
>original, thinking that that was the problem, but it is persisting.
>Here are the symptoms: The pressure gauge on the unit shows 30psi
>which is the burst point for the pressure valve, hence the leak. If I
>trigger the valve and fill up a bucket with water, I can get the
>pressure gauge down to around zero, but within an hour it's back up to
>30psi. I think the problem may be that the water supply valve to the
>furnace has failed, allowing water to get by and raise the pressure.
>Does that sound right? It feels like there's water flowing in the
>supply line after I trigger the pressure relief valve, but the supply
>has a ball valve, and I thought those things never failed...Could
>there be some grit or corrosion in it? I want to make sure I
>eliminate other possibilities before I cut the valve out and replace
>it.
>
>Thanks, Andrew

Sounds very much as if your expansion tank is full of water. What to do about it
depends on the type of expansion tank you have. For mine, I shut a valve leading
to the tank, and then there is a valve on the tank that I open to drain out the
water. I have a short length of garden hose that I attach to that valve so I can
direct the water into a bucket.

CWM

Posted by Andrew on March 4, 2007, 2:51 pm


>
>
>
> >The pressure overflow valve on my furnace is leaking. It's a gas
> >fired hot water radiator system. I recently replaced the corroded
> >original, thinking that that was the problem, but it is persisting.
> >Here are the symptoms: The pressure gauge on the unit shows 30psi
> >which is the burst point for the pressure valve, hence the leak. If I
> >trigger the valve and fill up a bucket with water, I can get the
> >pressure gauge down to around zero, but within an hour it's back up to
> >30psi. I think the problem may be that the water supply valve to the
> >furnace has failed, allowing water to get by and raise the pressure.
> >Does that sound right? It feels like there's water flowing in the
> >supply line after I trigger the pressure relief valve, but the supply
> >has a ball valve, and I thought those things never failed...Could
> >there be some grit or corrosion in it? I want to make sure I
> >eliminate other possibilities before I cut the valve out and replace
> >it.
>
> >Thanks, Andrew
>
> Sounds very much as if your expansion tank is full of water. What to do about
it
> depends on the type of expansion tank you have. For mine, I shut a valve
leading
> to the tank, and then there is a valve on the tank that I open to drain out the
> water. I have a short length of garden hose that I attach to that valve so I
can
> direct the water into a bucket.
>
> CWM

Okay, I hadn't considered a failure in the expansion tank. Mine is
not isolated by a control valve, and there's no way to drain the water
from it without taking it off the system, and that would require
draining the whole thing. It DOES have a schraeder valve, however.
When I activated that valve with my fingernail, air came out and
lowered the pressure in the system (as registered on the pressure
gauge). And now the leak seems to have stopped and that lower
pressure has been maintained. Could this have been my problem all
along? Would excess air in the system find its way into the expansion
tank and stay there? I guess I'm not sure how that would happen. Any
idea what this symptom would suggest? The tank is clearly not full of
water, since some air at least came out, but is this a sign of failure
nevertheless?


Page 2 of 2       << first < 1 2
Similar ThreadsPosted
Pressure Valve Leaking November 29, 2005, 7:08 pm
Question about water heater pressure relief valve is leaking March 23, 2006, 12:38 am
which ball valve - high pressure or low pressure? July 29, 2005, 3:11 am
How to fix leaking valve May 28, 2007, 9:52 pm
Will my valve remain not leaking? February 14, 2006, 1:57 pm
Well pressure tank leaking..... April 16, 2006, 3:53 am
Brand new leaking gate valve February 15, 2005, 10:08 pm
Leaking shut-off valve - emergency fix? October 30, 2005, 9:21 pm
Automatic sprinkler valve leaking July 23, 2006, 4:14 pm
fluidmaster constantly leaking from top of valve October 10, 2006, 2:13 am

Contact Us | Privacy Policy

XML SitemapXML Sitemap