Posted by Mark Lloyd on January 10, 2007, 11:14 am
On Tue, 09 Jan 2007 14:17:06 -0600, "dclutch"
>On my old GFCI the Line wires and Load wires are spliced together and
>pigtailed into the GFCI to not protect the outlets downstream. I'm trying
>to install a Leviton GFCI with Smartlock and when I try to wire it the
>same way it will not reset. I do not want to protect the outlets
>downstream of the GFIC. Is there a way around this? David Jasinski
That shouldn't happen if you connect it properly. Connect everything
to the LINE terminals on the GFCI and nothing to the LOAD terminals.
--
Mark Lloyd