Posted by D J on June 12, 2008, 1:43 pm
Hi all,
thanks so much for all your advise and such, now I am upto a point
where I have permit and ready for inspection. I have been testing the
line for pressure test but now for final inspection i have a
question.
do i need to connect all the appliances and shut off the valve to do
the PSI test? or without the appliances connected?
Also, I have put the pressure gas at the meter side. would it be ok OR
i need to do it from appliance end?
thanks,
DJ
|
|
Posted by franz fripplfrappl on June 12, 2008, 1:55 pm
On Thu, 12 Jun 2008 10:43:06 -0700, D J wrote:
> Hi all,
>
> thanks so much for all your advise and such, now I am upto a point where
> I have permit and ready for inspection. I have been testing the line for
> pressure test but now for final inspection i have a question.
>
> do i need to connect all the appliances and shut off the valve to do the
> PSI test? or without the appliances connected?
>
> Also, I have put the pressure gas at the meter side. would it be ok OR i
> need to do it from appliance end?
>
> thanks,
> DJ
I would do the test without appliances connected. The purpose of the
test seems to be to check for leaks in the supply line. n'est ce pas?
--
=================================================
Franz Fripplfrappl
|
|
Posted by Wayne Whitney on June 12, 2008, 1:56 pm
> do i need to connect all the appliances and shut off the valve to do
> the PSI test? or without the appliances connected?
All appliances and the meter itself should be disconnected for a
pressure test. High pressure will damage an appliance or the meter.
Just having an isolation valve in the off position is not considered
sufficient separation, because of the possibility of the valve the
leaking--they need to be phyiscally disconnected.
> Also, I have put the pressure gas at the meter side. would it be ok OR
> i need to do it from appliance end?
Once everything is disconnected, it doesn't matter.
Cheers, Wayne
|
|
Posted by Bob F on June 12, 2008, 4:15 pm
> Hi all,
>
> thanks so much for all your advise and such, now I am upto a point
> where I have permit and ready for inspection. I have been testing the
> line for pressure test but now for final inspection i have a
> question.
>
> do i need to connect all the appliances and shut off the valve to do
> the PSI test? or without the appliances connected?
>
> Also, I have put the pressure gas at the meter side. would it be ok OR
> i need to do it from appliance end?
The few times I've done it, it was with appliances not connected.
Your best bet is to ask the inspector.
|
|
Posted by S. Barker on June 13, 2008, 2:07 pm
You're best to leave the appliances disconnected. That way there's no
chance you apply the 10psi to the gas valves. They don't like that.
Especially on furnaces and water heaters. Apply the pressure where ever it
is handy. Normally, you would apply the pressure and have a guage t'd in
right outside where the line comes into the house.
s
> Hi all,
>
> thanks so much for all your advise and such, now I am upto a point
> where I have permit and ready for inspection. I have been testing the
> line for pressure test but now for final inspection i have a
> question.
>
> do i need to connect all the appliances and shut off the valve to do
> the PSI test? or without the appliances connected?
>
> Also, I have put the pressure gas at the meter side. would it be ok OR
> i need to do it from appliance end?
>
> thanks,
> DJ
|
| Similar Threads | Posted | | 2nd plumbing air pressure test | June 1, 2006, 1:10 pm |
| how to run at test at gas line to gas pack | November 30, 2007, 3:16 pm |
| Natural Gas Piping Pressure Test | February 6, 2006, 12:55 pm |
| Pool plumbing pressure test | October 27, 2006, 11:29 am |
| What equipment is required for pressure test? | September 28, 2007, 10:46 am |
| how to test gas copper line for leaks | January 20, 2006, 1:02 pm |
| Black Pipe pressure test - lost 0.5 PSI Over night | May 11, 2008, 11:39 am |
| Black Pipe pressure test - lost 0.5 PSI Over night | May 11, 2008, 11:40 am |
| Pressure tank installation | April 2, 2006, 4:02 pm |
| A/C installation -- Refrigerant pressure gauge | August 6, 2006, 9:53 am |
|
|