Posted by Peter H on February 14, 2005, 10:27 pm
I'm hoping someone in this group will take the time to answer this for me.
I'm in the middle of a course on HVAC in high-rises. The instructor has
stated that the oil in the HVAC system should be checked regularly for
quality and impurities. She says that if refrigerant is detected in the oil
then there is a problem. I was always thought that there is oil in the
system with the refrigerant and that this oil lubricated the compressor
etc.and one would expect to find refrigerant mixed in with it. I thought
that this was why you are always told to let a newly delivered fridge stand
for an hour or two before turning it on, to let the oil drain back down into
the compressor.
What gives?
tia
Peter H
|

| |
Posted by Dr. Hardcrab on February 15, 2005, 5:07 am
> I'm hoping someone in this group will take the time to answer this for me.
>
> I'm in the middle of a course on HVAC in high-rises. The instructor has
> stated that the oil in the HVAC system should be checked regularly for
> quality and impurities. She says that if refrigerant is detected in the
> oil
> then there is a problem. I was always thought that there is oil in the
> system with the refrigerant and that this oil lubricated the compressor
> etc.and one would expect to find refrigerant mixed in with it. I thought
> that this was why you are always told to let a newly delivered fridge
> stand
> for an hour or two before turning it on, to let the oil drain back down
> into
> the compressor.
>
> What gives?
>
Sounds like your teacher needs to be a little more clearer on her
explaination OR you need to get another teacher.....
|
|
Posted by Stormin Mormon on February 15, 2005, 6:45 am
Those big skyscrapers sometimes use semihermetic compresssors (like boat
motors, or car engines). Which have a crankcase for the oil.
Refrigerators do mix the oil and refrigerant, and so for refrig, that's
normal.
As to mixing th eoil and refrigerant, that's a new one to me, I do mostly
small stuff, not skyscrapers.
As for the new fridge, I think the major problem is oil in the piston. Cause
oil isn't compressable. I've seen a couple cases where folks tipped a fridge
to move it. When they plugged it right back in, it killed the compressor.
--
Christopher A. Young
Learn more about Jesus
www.lds.org
www.mormons.com
I'm hoping someone in this group will take the time to answer this for me.
I'm in the middle of a course on HVAC in high-rises. The instructor has
stated that the oil in the HVAC system should be checked regularly for
quality and impurities. She says that if refrigerant is detected in the oil
then there is a problem. I was always thought that there is oil in the
system with the refrigerant and that this oil lubricated the compressor
etc.and one would expect to find refrigerant mixed in with it. I thought
that this was why you are always told to let a newly delivered fridge stand
for an hour or two before turning it on, to let the oil drain back down into
the compressor.
What gives?
tia
Peter H
|
|
Posted by Barr on February 15, 2005, 10:40 pm
On Tue, 15 Feb 2005 03:45:29 GMT, "Stormin Mormon"
>Those big skyscrapers sometimes use semihermetic compresssors (like boat
>motors, or car engines). Which have a crankcase for the oil.
>
>Refrigerators do mix the oil and refrigerant, and so for refrig, that's
>normal.
>
>As to mixing th eoil and refrigerant, that's a new one to me, I do mostly
>small stuff, not skyscrapers.
>
>As for the new fridge, I think the major problem is oil in the piston. Cause
>oil isn't compressable. I've seen a couple cases where folks tipped a fridge
>to move it. When they plugged it right back in, it killed the compressor.
I know I should comment on this post but, I won't. Just
disreguard. There is no useful information in this fallow up.
Barry
|
|
Posted by Geoman on February 15, 2005, 3:30 pm
> I'm hoping someone in this group will take the time to answer this for me.
>
> I'm in the middle of a course on HVAC in high-rises. The instructor has
> stated that the oil in the HVAC system should be checked regularly for
> quality and impurities.
Yes, you can take oil samples and send them in to labs. These tests can,
depending on what you want tested, show if the compressor is running hot or
if there is some flooding, moisture, acid and other issues.
She says that if refrigerant is detected in the oil
> then there is a problem.
I thhink she's talking about liquid here. You will always have some
refrigerant in the oil but saturated with refrigerant is a big problem. This
can result from migration or flood back.
I was always thought that there is oil in the
> system with the refrigerant and that this oil lubricated the compressor
> etc.and one would expect to find refrigerant mixed in with it. I thought
> that this was why you are always told to let a newly delivered fridge
> stand
> for an hour or two before turning it on, to let the oil drain back down
> into
> the compressor.
I was told to let it settle down because of debris in the crankcase being
disturbed coud plug the cap tube. It doesn't matter for me because I always
heat the compressor up before plugging ours in.
I'm surprised she didn't mention a MegOhm reading being taken and logged as
well.
The reason she is talking about these topics is with typical large highrises
the compressors are very expensive. Parts can be limited if its an older or
specialty brand. It is normal to test centrifugals and screw compressors. I
remember before oil testing we would change the York centrifugals oil out
every year and hoped that it didn't need it more. Testing the oil took the
guess work out.
I also think its wise to check the quantity of oil in the system.
>
> What gives?
>
> tia
>
> Peter H
>
>
>
|
| Similar Threads | Posted | | hvac question | July 15, 2005, 2:43 pm |
| HVAC question | September 20, 2005, 2:28 pm |
| HVAC question | February 13, 2006, 8:39 pm |
| HVAC Question. | July 21, 2006, 6:44 pm |
| HVAC Question | January 2, 2007, 6:42 pm |
| hvac question | October 24, 2007, 11:37 am |
| HVAC question | May 26, 2008, 3:23 pm |
| A question for the HVAC guys | December 29, 2005, 7:29 pm |
| hvac ductwork question | August 3, 2006, 9:15 pm |
| HVAC Hard start cap question | July 15, 2005, 9:04 am |
|
|
|