Half of breaker panel hot, the other dead!?!

Home Repair - - If it ain't broken, don't fix it. Otherwise look here. 

Page 1 of 4       1 2 3 > last >> Bookmark this page:  YahooMyWeb Yahoo!  Google Google  Windows Live Favorites Windows Live  del.icio.us del.icio.us  digg digg  Add to Netscape Netscape
Subject Author Date
Half of breaker panel hot, the other dead!?! SpyOwns 09-22-2006
If you were  Registered and logged in, you could reply and use other advanced thread options
Posted by on September 22, 2006, 11:28 pm
One side of my breaker panel is hot and the other is dead. What could
be a possible cause of this?


PexSupply Full Banner
Posted by Tony Hwang on September 22, 2006, 11:37 pm
SpyOwns@gmail.com wrote:
> One side of my breaker panel is hot and the other is dead. What could
> be a possible cause of this?
>
Hi,
First, sounds like one leg of 220V coming in is dead.
If you have a meter check it out.

Posted by hallerb@aol.com on September 22, 2006, 11:47 pm

try reseting main breaker, ask neighbors one leg of 120 may be out from
things like transformer failure


Posted by Toller on September 23, 2006, 12:30 am

> SpyOwns@gmail.com wrote:
>> One side of my breaker panel is hot and the other is dead. What could
>> be a possible cause of this?
>>
> Hi,
> First, sounds like one leg of 220V coming in is dead.
> If you have a meter check it out.

Or your main breaker is bad, or a wire has come loose. Won't know until you
check to see where where you have voltage.



Posted by Tim Fischer on September 23, 2006, 12:52 am

> One side of my breaker panel is hot and the other is dead. What could
> be a possible cause of this?

I'd agree with the others, that it sounds like you've 'lost a leg', but...

Do you reall mean "one side" as in "of the two rows of breakers, the one on
the left/right works and the other doesn't", or that every other breaker
doesn't work?

The latter would be a symptom of losing a leg. The former would be just
weird...

-Tim



Page 1 of 4       1 2 3 > last >>
Similar ThreadsPosted
Main Breaker Tripping - But Only Half May 19, 2006, 2:58 am
dead mice in electrical panel!!! February 17, 2007, 7:56 pm
Dead circuit with no tripped breaker or fuse July 19, 2007, 8:39 pm
Extending a Breaker Panel. September 9, 2005, 12:58 pm
Breaker Panel....Neutral bus March 11, 2006, 8:03 pm
Found something odd in my breaker panel October 5, 2006, 4:59 pm
200 amp main panel with 100 amp breaker May 27, 2008, 8:39 am
Circuit breaker panel question December 12, 2006, 5:21 pm
Circuit Breaker Panel Question December 12, 2007, 12:14 pm
Breaker Panel 220V problem January 6, 2008, 3:38 pm

Contact Us | Privacy Policy

XML SitemapXML Sitemap