Posted by fconsig on February 22, 2008, 10:31 am
I have a newish gas forced hot water heating system that is talking
hours to move the temp in the house a few degrees. The house it
small, 1000 sf, and tight and it is only 30 degrees out.

My heating system has one Taco cartridge circulator 007-F5 and the
body of the cartridge is extremely hot and it is silent except for a
little hum on the electrical control. It is placed on the return side
of the line and there the line is warm but not hot. The radiators are
warm but not hot.

Is this normal?

Thanks

fconsig at yahoo dot com

Special 468x60
Posted by on February 22, 2008, 10:45 am
On Fri, 22 Feb 2008 07:31:27 -0800 (PST), fconsig

>I have a newish gas forced hot water heating system that is talking
>hours to move the temp in the house a few degrees. The house it
>small, 1000 sf, and tight and it is only 30 degrees out.
>
>My heating system has one Taco cartridge circulator 007-F5 and the
>body of the cartridge is extremely hot and it is silent except for a
>little hum on the electrical control. It is placed on the return side
>of the line and there the line is warm but not hot. The radiators are
>warm but not hot.
>
>Is this normal?
>
>Thanks
>
>fconsig at yahoo dot com

It's normal for the circulator to be as you described it. If your
radiators are not getting hot, maybe there is an air pocket at some
point and the system needs bleeding. Why it would develop an air
pocket would be another question.



Posted by Edwin Pawlowski on February 22, 2008, 11:02 pm

> On Fri, 22 Feb 2008 07:31:27 -0800 (PST), fconsig
>
>>I have a newish gas forced hot water heating system that is talking
>>hours to move the temp in the house a few degrees. The house it
>>small, 1000 sf, and tight and it is only 30 degrees out.
>>
>>My heating system has one Taco cartridge circulator 007-F5 and the
>>body of the cartridge is extremely hot and it is silent except for a
>>little hum on the electrical control. It is placed on the return side
>>of the line and there the line is warm but not hot. The radiators are
>>warm but not hot.
>>
>>Is this normal?

Could be a few things.

Yes, the motor will get reasonably hot both from running and from the hot
water that should be going through it. The 07 is a very popular and
reliable circulator. Do you feel it running? The hum can be the noise of
the pump, or it could be the noise of a stalled motor.

Is the water feed to the boiler open? If not, it may be low on water and
the pump is just spinning and not moving any water. If the circulator is
bad, it is a quick change to a new one. Taco is good, but there are other
brands that will fit in the same space. Just be sure if the electrical
conection is in a idfferent place there is no obstructin the way it is
mounted.




Posted by RBM on February 22, 2008, 10:54 am



>I have a newish gas forced hot water heating system that is talking
> hours to move the temp in the house a few degrees. The house it
> small, 1000 sf, and tight and it is only 30 degrees out.
>
> My heating system has one Taco cartridge circulator 007-F5 and the
> body of the cartridge is extremely hot and it is silent except for a
> little hum on the electrical control. It is placed on the return side
> of the line and there the line is warm but not hot. The radiators are
> warm but not hot.
>
> Is this normal?
>
> Thanks
>
> fconsig at yahoo dot com

Those circulators do get really hot and there's no way to physically tell,
by vibrations, if they are circulating. Assuming that the house is just one
zone, with one circulator, and the pump is returning water to the boiler:
After a couple of minutes at most, the pipe between the circulator and the
boiler should be at about the same temp as the boiler. There may be air in
the system, or possibly the boiler temp is set to low



Posted by ransley on February 22, 2008, 10:55 am
> I have a newish gas forced hot water heating system that is talking
> hours to move the temp in the house =A0a few degrees. The house it
> small, 1000 sf, and tight and it is only 30 degrees out.
>
> My heating system has one Taco cartridge circulator 007-F5 and the
> body of the cartridge is extremely hot and it is silent except for a
> little hum on the electrical control. It is placed on the return side
> of the line and there the line is warm but not hot. =A0The radiators are
> warm but not hot.
>
> Is this normal?
>
> Thanks
>
> fconsig at yahoo dot com

How new is new, you have a warranty, what is boiler temp, find out if
the pump runs. Turn down the aquastat on the boiler after the boiler
is hot, as low as it goes, lower than the boiler temp but keep the
thermostat calling for heat so the boiler doesnt fire but pump will
run. Bleed radiators and be sure pump is pumping.

Similar ThreadsPosted
hydronic heating circulator question December 24, 2006, 1:43 pm
Followup Question on Water Filter Cartridge Replacement January 7, 2007, 11:28 am
wiring a taco relay for a closet light switch March 24, 2006, 10:05 pm
Re: President Taco Breath to mumble Monday night on immigration. May 12, 2006, 3:21 pm
Used circulator July 28, 2006, 12:23 pm
MOEN cartridge or another? January 13, 2008, 6:14 pm
Wait Circulator October 31, 2006, 8:57 pm
Moen cartridge for other brands? May 29, 2006, 5:41 pm
Jado faucet cartridge June 10, 2007, 9:07 pm
Moen 1200 Cartridge - Which way is up? December 30, 2007, 5:22 pm

Contact Us | Privacy Policy

XML SitemapXML Sitemap