Posted by Doug on October 9, 2006, 2:14 am
A friend of mine has a large (4000 sq.ft.) home built in 1950.
It's in New England with a concrete slab on grade construction. There
is a small basement under about 10% of the house containing the
heating boiler and the beginning of plumbing loops.
The house has radiant heating with copper pipe buried in the concrete.
There are also 4 baths and two sink kitchen areas with all supply and
drain piping also buried in the concrete.
My friend lost one of the radiant loops about two years ago and heard
water sprying out of the loop via a burst pipe under the concrete. The
water was geysering out from under the foundation to the outside. She
installed a new hydro-air heating system in that part of the building
to replace that lost loop. The leaking loop was blocked off and
abandoned. The cost was over $17,000 but insurance picked up part of
the price. The new system only covers about 1000 sq ft of the home
with the remaining radiant loops still heating the rest of the place.
To me the house is a nightmare waiting to happen with most likely
frequent plumbing and heating loop failures in the near future with
absolutely NO access without jackhammering up the concrete.
I'm amazed that the copper has lasted in damp concrete for the 56
years that it has...
Anyone seen a situation like this?
So far, we've not even found tradesmen willing to get involved.
I'm tempted to advise her to start a replacement program, jack
hammering up pipe runs to each bath, one room at a time.
However, most of the flooring has beautiful tiling and she's reluctant
to damage that. There's a shallow attic over only part of the house,
where they've installed the hydro air system. Due to the almost
impossible access I can see why they didn't make the new system more
extensive.
My friend is more house rich and cash poor. She has some budget room
but it's not unlimited.
Any ideas? I shake my head when I'm in the place wondering what the
original builders were thinking.
Doug
|
|
Posted by buffalobill on October 9, 2006, 3:21 am
9-volt battery water alarms are $10 at home depot.
it's surprising but our 1910 houses in this area of buffalo ny still
have galvanized water pipes in use in parts of the water systems.
especially where you have fears, install an electronic water alarm
system and a $100 dialer to call your cellphone so you can promptly
respond to minimize water damage.
in this case the "don't fix it if it ain't broke" may apply due to the
budget.
the type of heating system to be installed usually will be dependent in
part on local energy costs and type of soil, attic versus utility room
concerns so the heating system will be indoors in conditioned space,
frozen pipe worries, central air conditioning needs, and always some
local requirements to meet building codes particular to the address and
type of construction and zoning.
in the meantime why not suggest a home improvement line of credit
application for some confidence on required upcoming repairs.
every house is a nightmare waiting to happen, but in the meantime enjoy
some sweet dreams with the new alarm system.
we've all got to live somewhere. :)
Doug wrote:
> A friend of mine has a large (4000 sq.ft.) home built in 1950.
> It's in New England with a concrete slab on grade construction. There
> is a small basement under about 10% of the house containing the
> heating boiler and the beginning of plumbing loops.
> The house has radiant heating with copper pipe buried in the concrete.
> There are also 4 baths and two sink kitchen areas with all supply and
> drain piping also buried in the concrete.
> My friend lost one of the radiant loops about two years ago and heard
> water sprying out of the loop via a burst pipe under the concrete. The
> water was geysering out from under the foundation to the outside. She
> installed a new hydro-air heating system in that part of the building
> to replace that lost loop. The leaking loop was blocked off and
> abandoned. The cost was over $17,000 but insurance picked up part of
> the price. The new system only covers about 1000 sq ft of the home
> with the remaining radiant loops still heating the rest of the place.
> To me the house is a nightmare waiting to happen with most likely
> frequent plumbing and heating loop failures in the near future with
> absolutely NO access without jackhammering up the concrete.
> I'm amazed that the copper has lasted in damp concrete for the 56
> years that it has...
> Anyone seen a situation like this?
> So far, we've not even found tradesmen willing to get involved.
> I'm tempted to advise her to start a replacement program, jack
> hammering up pipe runs to each bath, one room at a time.
> However, most of the flooring has beautiful tiling and she's reluctant
> to damage that. There's a shallow attic over only part of the house,
> where they've installed the hydro air system. Due to the almost
> impossible access I can see why they didn't make the new system more
> extensive.
> My friend is more house rich and cash poor. She has some budget room
> but it's not unlimited.
> Any ideas? I shake my head when I'm in the place wondering what the
> original builders were thinking.
>
> Doug
|
|
Posted by HeatMan on October 9, 2006, 11:34 pm
So, what are you asking? Replacing the radiant or re-plumbing the house?
If there is a question about the re-plumbing, go overhead! Water lines can
be run in an attic, you just have to be careful about making sure they are
insulated well.
> A friend of mine has a large (4000 sq.ft.) home built in 1950.
> It's in New England with a concrete slab on grade construction. There
> is a small basement under about 10% of the house containing the
> heating boiler and the beginning of plumbing loops.
> The house has radiant heating with copper pipe buried in the concrete.
> There are also 4 baths and two sink kitchen areas with all supply and
> drain piping also buried in the concrete.
> My friend lost one of the radiant loops about two years ago and heard
> water sprying out of the loop via a burst pipe under the concrete. The
> water was geysering out from under the foundation to the outside. She
> installed a new hydro-air heating system in that part of the building
> to replace that lost loop. The leaking loop was blocked off and
> abandoned. The cost was over $17,000 but insurance picked up part of
> the price. The new system only covers about 1000 sq ft of the home
> with the remaining radiant loops still heating the rest of the place.
> To me the house is a nightmare waiting to happen with most likely
> frequent plumbing and heating loop failures in the near future with
> absolutely NO access without jackhammering up the concrete.
> I'm amazed that the copper has lasted in damp concrete for the 56
> years that it has...
> Anyone seen a situation like this?
> So far, we've not even found tradesmen willing to get involved.
> I'm tempted to advise her to start a replacement program, jack
> hammering up pipe runs to each bath, one room at a time.
> However, most of the flooring has beautiful tiling and she's reluctant
> to damage that. There's a shallow attic over only part of the house,
> where they've installed the hydro air system. Due to the almost
> impossible access I can see why they didn't make the new system more
> extensive.
> My friend is more house rich and cash poor. She has some budget room
> but it's not unlimited.
> Any ideas? I shake my head when I'm in the place wondering what the
> original builders were thinking.
> Doug
|
|
Posted by Doug on October 10, 2006, 2:23 am
On Mon, 9 Oct 2006 23:34:40 -0400, "HeatMan"
>So, what are you asking? Replacing the radiant or re-plumbing the house?
Both - since they are equally problematic.
>If there is a question about the re-plumbing, go overhead! Water lines can
>be run in an attic, you just have to be careful about making sure they are
>insulated well.
Perhaps, that's where the hydro-air system was installed.
However, most of the house has no attic.
This is a Frank Lloyd Wright type of contemporary home, with a tilted
flat roof. The attic is under the high part but most of the house has
no attic. Most of the walls have floor to ceiling windows so pipes can
not be run horizontally across walls without really major rework.
Doug
>> A friend of mine has a large (4000 sq.ft.) home built in 1950.
>> It's in New England with a concrete slab on grade construction. There
>> is a small basement under about 10% of the house containing the
>> heating boiler and the beginning of plumbing loops.
>> The house has radiant heating with copper pipe buried in the concrete.
>> There are also 4 baths and two sink kitchen areas with all supply and
>> drain piping also buried in the concrete.
>> My friend lost one of the radiant loops about two years ago and heard
>> water sprying out of the loop via a burst pipe under the concrete. The
>> water was geysering out from under the foundation to the outside. She
>> installed a new hydro-air heating system in that part of the building
>> to replace that lost loop. The leaking loop was blocked off and
>> abandoned. The cost was over $17,000 but insurance picked up part of
>> the price. The new system only covers about 1000 sq ft of the home
>> with the remaining radiant loops still heating the rest of the place.
>> To me the house is a nightmare waiting to happen with most likely
>> frequent plumbing and heating loop failures in the near future with
>> absolutely NO access without jackhammering up the concrete.
>> I'm amazed that the copper has lasted in damp concrete for the 56
>> years that it has...
>> Anyone seen a situation like this?
>> So far, we've not even found tradesmen willing to get involved.
>> I'm tempted to advise her to start a replacement program, jack
>> hammering up pipe runs to each bath, one room at a time.
>> However, most of the flooring has beautiful tiling and she's reluctant
>> to damage that. There's a shallow attic over only part of the house,
>> where they've installed the hydro air system. Due to the almost
>> impossible access I can see why they didn't make the new system more
>> extensive.
>> My friend is more house rich and cash poor. She has some budget room
>> but it's not unlimited.
>> Any ideas? I shake my head when I'm in the place wondering what the
>> original builders were thinking.
>> Doug
|
|
Posted by Goedjn on October 10, 2006, 10:37 am
>>> I'm tempted to advise her to start a replacement program, jack
>>> hammering up pipe runs to each bath, one room at a time.
>>> However, most of the flooring has beautiful tiling and she's reluctant
>>> to damage that. There's a shallow attic over only part of the house,
>>> where they've installed the hydro air system. Due to the almost
>>> impossible access I can see why they didn't make the new system more
>>> extensive.
>>> My friend is more house rich and cash poor. She has some budget room
>>> but it's not unlimited.
>>> Any ideas? I shake my head when I'm in the place wondering what the
>>> original builders were thinking.
Probably that the house would last a generation or so, after which
it's likely to get bulldozed and replaced.
At some point, the roof is going to need to be re-done.
That would be an excellent time to put in overhead piping
to all the plumbing fixtures. Alternatively, spend a lot
of time digging pits in the yard, and drill horizontally
under the slab to get pipe runs where you want them.
Which leaves only the
radiant floor-heating to worry about.
Annodes would probably extend the life of that system,
but in the long run, I think you're (she's) going to
have to either abandon it in place, or dig up the
floors. If you're lucky, by the time another section
fails, someone will have invented a little pipe-crawling
robot that will follow all the loops, and epoxy them from
the inside. Are the existing pipes big enough that
pulling plastic tubing through them is plausible?
What would that do to the heat-transfer out of the
tubes, and does that really matter?
Hmmm...
Flush a wad of cotton pulling a string through a loop.
Use the string to pull a cable. Use the cable to
pull a reamer (Or somthing that dissolved copper
pipe fast.) , then feed plastic tubing, pressurize the
tube, squirt (really thin) epoxy in around the OUTSIDE
of the tube, depressurize after the epoxy sets, connect the
tubing to the heating system. This is do-able.
Maybe you'd want to coat the inside of the pathway with
long-cure epoxy before pulling the tubing.
--Goedjn
|
Page 1 of 2 1 2 > last >>
| Similar Threads | Posted | | Problems Heating House - Apollo Heating System. | November 2, 2008, 3:26 pm |
| "Portable" radiant heating | January 23, 2008, 2:43 pm |
| getting pex for staple-up radiant to heating area | August 26, 2005, 11:27 am |
| Oxygen In Radiant Floor Heating | September 6, 2006, 7:32 am |
| Adding underfloor radiant heating with PEX? | March 1, 2007, 2:28 pm |
| Radiant Floor heating - nonliquid? | September 21, 2008, 1:57 pm |
| Radiant ceiling heating cable | March 26, 2009, 12:56 pm |
| Radiant Floor Heating added in a 100-yr old house | December 19, 2005, 11:18 am |
| plumbing problems | November 19, 2005, 9:02 am |
| Hot Water Plumbing Problems | July 2, 2009, 3:24 am |
|
|
> It's in New England with a concrete slab on grade construction. There
> is a small basement under about 10% of the house containing the
> heating boiler and the beginning of plumbing loops.
> The house has radiant heating with copper pipe buried in the concrete.
> There are also 4 baths and two sink kitchen areas with all supply and
> drain piping also buried in the concrete.
> My friend lost one of the radiant loops about two years ago and heard
> water sprying out of the loop via a burst pipe under the concrete. The
> water was geysering out from under the foundation to the outside. She
> installed a new hydro-air heating system in that part of the building
> to replace that lost loop. The leaking loop was blocked off and
> abandoned. The cost was over $17,000 but insurance picked up part of
> the price. The new system only covers about 1000 sq ft of the home
> with the remaining radiant loops still heating the rest of the place.
> To me the house is a nightmare waiting to happen with most likely
> frequent plumbing and heating loop failures in the near future with
> absolutely NO access without jackhammering up the concrete.
> I'm amazed that the copper has lasted in damp concrete for the 56
> years that it has...
> Anyone seen a situation like this?
> So far, we've not even found tradesmen willing to get involved.
> I'm tempted to advise her to start a replacement program, jack
> hammering up pipe runs to each bath, one room at a time.
> However, most of the flooring has beautiful tiling and she's reluctant
> to damage that. There's a shallow attic over only part of the house,
> where they've installed the hydro air system. Due to the almost
> impossible access I can see why they didn't make the new system more
> extensive.
> My friend is more house rich and cash poor. She has some budget room
> but it's not unlimited.
> Any ideas? I shake my head when I'm in the place wondering what the
> original builders were thinking.
>
> Doug