Posted by timmacrina@gmail.com on June 13, 2007, 10:24 am
I am installing a temporary subpanel for a large outdoor christmas
light display. I plan on running two hots and a neutral to the
subpanel. I know that you do not tie the ground and neutral together
in a subpanel like you do in a main panel so my question is Do I need
to run a ground from my main panel to my subpanel if I plan on
installing a seperate grounding rod for the subpanel?


Posted by Doug Miller on June 13, 2007, 11:48 am
>I am installing a temporary subpanel for a large outdoor christmas
>light display. I plan on running two hots and a neutral to the
>subpanel. I know that you do not tie the ground and neutral together
>in a subpanel like you do in a main panel so my question is Do I need
>to run a ground from my main panel to my subpanel if I plan on
>installing a seperate grounding rod for the subpanel?

Yes.

--
Regards,
Doug Miller (alphageek at milmac dot com)

It's time to throw all their damned tea in the harbor again.

Posted by sylvan butler on June 13, 2007, 7:53 pm
wrote:
> I am installing a temporary subpanel for a large outdoor christmas
> light display. I plan on running two hots and a neutral to the

That must be the 240v "two hots" from a dual (ganged) breaker.

> subpanel. I know that you do not tie the ground and neutral together
> in a subpanel like you do in a main panel so my question is Do I need
> to run a ground from my main panel to my subpanel if I plan on
> installing a seperate grounding rod for the subpanel?

Where is the subpanel being installed?

If it is in a seperate building, with NO conductors (other than the
2xHot and Neutral) connecting the two buildings, no plumbing, no air
vents, etc. then no ground line is needed. Do bond the neutral and
ground in the subpanel.

Otherwise you must run a ground line, usually #6 or larger and do not
bond neutral and ground in the subpanel.

sdb
--
What's seen on your screen? http://pcscreenwatch.com
sdbuse1 on mailhost bigfoot.com

Similar ThreadsPosted
How to ground a cable feed? December 5, 2005, 5:19 pm
Outdoor telephone cable repair advise needed July 10, 2005, 6:57 pm
Ground level flooring advice needed October 12, 2006, 10:15 am
2 "ground rod" questions (Thumper aka cable fault locator) December 14, 2006, 11:10 pm
Outcome (was 2 "ground rod" questions (Thumper aka cable fault locator)) December 16, 2006, 6:28 pm
Intermittent static when viewing cable, cable ready problem? October 9, 2005, 7:14 am
Is it safe to assume RG6 cable strippers and cable connectors are going to be compatible? November 19, 2005, 5:19 pm
Cable TV and coax splitters - Hookup splitter to Digital Cable August 23, 2007, 4:23 pm
Burial cable vs normal cable in conduit September 27, 2005, 11:19 pm
Bonded ground wires vs. earth ground wire December 25, 2006, 6:08 pm

Contact Us | Privacy Policy

XML SitemapXML Sitemap