Posted by caudiar777 on June 9, 2006, 1:46 am
Thank you for the quick response. I did find out that the wire that was
wired together in the back must have been L2 and T2 tied together
already, and that L1 and T1 were being broken by the old thermostat. I
untied the back wires, connected the two hots to L1-L2 and the two
obvious ceiling heat wires (thick red) to the T1 and T2..
Thank you again..
RBM Wrote:
> Your thermostat has L1-L2 and T1-T2. Wirenut L1,L2 and one wire from the
> old
> stat together, then wire T1, T2 and the other wire from the old stat
> together
>
>
>
> "caudiar777" caudiar777.293owu@diybanter.com wrote in message
>
> I've read that the 4-wire (double pole?) is usually the preferred
> method
> for connecting 240V line voltage thermostats and I have a 240V
> radiant
> ceiling heat. I bought several Honeywell CT1950B (4 wire)
> thermostats
> and when I pulled my old (circa 1970) thermostat off of the wall I
> noticed it had 2 wires, a red and a black, with 1 white wire wired in
> the back of the box (kind of like a neutral wire for a 110V light
> switch connection).. Is it possible to use these 4-wire thermos
> given
> my current situation? Any wiring tricks to hook up 2 wires here or
> there? (I know I'm probably over simplifying).. If anyone can provide
> me help here I would greatly appreciate it.
>
> Thank you
>
>
> --
> caudiar777
--
caudiar777
|