Posted by Woody2 on December 11, 2006, 2:30 pm


I am going to have a 200amp. heavy up done , but later plan to add to
Garage/worshop area. What type of wire is suitable for use of air compressor
rated @ 20amp. also would like to add overhead flurosent light, run power
saws grinder etc. Should I have dedicated circuits, please advise best route
to go.
Thanks Woody2


Real Goods Solar, Inc.
Posted by N8N on December 11, 2006, 2:42 pm



Woody2 wrote:
> I am going to have a 200amp. heavy up done , but later plan to add to
> Garage/worshop area. What type of wire is suitable for use of air compressor
> rated @ 20amp. also would like to add overhead flurosent light, run power
> saws grinder etc. Should I have dedicated circuits, please advise best route
> to go.
> Thanks Woody2

For a workshop area, I would plan on having several spare 20A breakers
available for installation of outlets etc. the more circuits the better
just in case you end up having a helper working in there with you and
you end up using two or more appliances simultaneously.

I'd keep the lighting separate from the receps. because eventually you
will trip a breaker no matter how well you plan, and it sucks finding
the door in the dark.

good luck

nate


Posted by Woody2 on December 11, 2006, 3:10 pm


Thanks Nate, do you have any recomendations as to wire size,and or breaker
amps. The main panel is about 100ft. from shop area.
Woody2

N8N wrote:
>> I am going to have a 200amp. heavy up done , but later plan to add to
>> Garage/worshop area. What type of wire is suitable for use of air compressor
>> rated @ 20amp. also would like to add overhead flurosent light, run power
>> saws grinder etc. Should I have dedicated circuits, please advise best route
>> to go.
>> Thanks Woody2
>
>For a workshop area, I would plan on having several spare 20A breakers
>available for installation of outlets etc. the more circuits the better
>just in case you end up having a helper working in there with you and
>you end up using two or more appliances simultaneously.
>
>I'd keep the lighting separate from the receps. because eventually you
>will trip a breaker no matter how well you plan, and it sucks finding
>the door in the dark.
>
>good luck
>
>nate


Posted by EXT on December 11, 2006, 4:12 pm


Run a heavy cable to the workshop and install a sub-panel in the workshop to
feed each circuit that you require.

> Thanks Nate, do you have any recomendations as to wire size,and or breaker
> amps. The main panel is about 100ft. from shop area.
> Woody2
>
> N8N wrote:
>>> I am going to have a 200amp. heavy up done , but later plan to add to
>>> Garage/worshop area. What type of wire is suitable for use of air
>>> compressor
>>> rated @ 20amp. also would like to add overhead flurosent light, run
>>> power
>>> saws grinder etc. Should I have dedicated circuits, please advise best
>>> route
>>> to go.
>>> Thanks Woody2
>>
>>For a workshop area, I would plan on having several spare 20A breakers
>>available for installation of outlets etc. the more circuits the better
>>just in case you end up having a helper working in there with you and
>>you end up using two or more appliances simultaneously.
>>
>>I'd keep the lighting separate from the receps. because eventually you
>>will trip a breaker no matter how well you plan, and it sucks finding
>>the door in the dark.
>>
>>good luck
>>
>>nate
>



Posted by RBM on December 11, 2006, 5:17 pm


If the compressor draws 20 amps, you will need a 30 amp cable to feed it.
That would be 10gauge wire. From what you describe of your shop, you would
do well to run a 6/3 feed from the main and install something like an 8
circuit sub panel in the shop, then run the machine outlets and lights from
the sub



>I am going to have a 200amp. heavy up done , but later plan to add to
> Garage/worshop area. What type of wire is suitable for use of air
> compressor
> rated @ 20amp. also would like to add overhead flurosent light, run power
> saws grinder etc. Should I have dedicated circuits, please advise best
> route
> to go.
> Thanks Woody2
>



Similar ThreadsPosted
Single Woman needs elec advice November 2, 2006, 12:42 pm
Elec. Disconnect box help June 18, 2007, 2:00 pm
outside elec. outlet exploded November 20, 2005, 4:13 am
Bathroom (elec.) Wiring for TV November 29, 2005, 5:48 pm
40 volts at one elec outlet January 10, 2007, 11:28 am
Elec code question September 18, 2007, 5:55 pm
Clean My Elec Stove? April 8, 2008, 9:51 am
Can anyone top this elec box repair estimate? October 18, 2008, 6:39 pm
Clearance in front of elec meter? August 3, 2005, 10:35 pm
Elec. Water Heater Leak March 2, 2008, 4:57 pm

Contact Us | Privacy Policy

XML SitemapXML Sitemap