Posted by brianv on April 11, 2008, 2:04 pm
Hi all. I have an older panel and I need to install a new one. I have only
1+ years experience with electric. The old panel is a Federal Pacific
125amp main lug. The service comes into the house to a 100amp main
breaker, then goes to the panel. I consulted an electrician and he told me
that I should get a 100amp main lug panel to replace it. He also said that
the neutral and ground bus bars should be separated and that new code
requires that a ground wire be attached to the main water pipes. I live in
Pennsylvania Montgomery County. I know I need a permit and inspection. Can
someone help me by giving a few details on things like the neutral bus and
ground bus deal? Also does a main lug panel need a 100amp breaker in it? I
don't want to remove the 100amp main disconnect and I assume that means
that the panel would be considered a sub panel? I am on a tight budget and
can't hire an electrician. Thank You.

-------------------------------------




##-----------------------------------------------##
Delivered via http://www.www.thestuccocompany.com/
Building Construction and Maintenance Forum
Web and RSS access to your favorite newsgroup -
alt.home.repair - 283959 messages and counting!
##-----------------------------------------------##

Posted by RBM on April 11, 2008, 4:52 pm

> Hi all. I have an older panel and I need to install a new one. I have only
> 1+ years experience with electric. The old panel is a Federal Pacific
> 125amp main lug. The service comes into the house to a 100amp main
> breaker, then goes to the panel. I consulted an electrician and he told me
> that I should get a 100amp main lug panel to replace it. He also said that
> the neutral and ground bus bars should be separated and that new code
> requires that a ground wire be attached to the main water pipes. I live in
> Pennsylvania Montgomery County. I know I need a permit and inspection. Can
> someone help me by giving a few details on things like the neutral bus and
> ground bus deal? Also does a main lug panel need a 100amp breaker in it? I
> don't want to remove the 100amp main disconnect and I assume that means
> that the panel would be considered a sub panel? I am on a tight budget and
> can't hire an electrician. Thank You.
>
> -------------------------------------
>
>
>
>
> ##-----------------------------------------------##
> Delivered via http://www.www.thestuccocompany.com/
> Building Construction and Maintenance Forum
> Web and RSS access to your favorite newsgroup -
> alt.home.repair - 283959 messages and counting!
> ##-----------------------------------------------##

A main lug panel is one that doesn't have a main breaker. you will not need
one in this case.Yes, leave the main breaker alone, get a 100 amp main lug
panel, and get an additional ground bar. As a sub panel the neutral and the
ground are kept separate. You will run a four wire feed from the 100 amp
disconnect to the sub panel. The neutral and ground conductors will attach
to the same location at the main breaker. In the sub panel the neutral
conductor goes to the neutral buss that came included in the panel, and the
ground conductor goes to the ground bar that you install. The panel will
come with a bonding jumper or screw that connects the neutral bar to the
panel box. DON'T use it.



Similar ThreadsPosted
Main panel to main panel wiring in converting multi-family to single family dwelling November 9, 2006, 6:35 pm
Main Panel and Sub Panel questions and the NEC March 31, 2008, 1:48 pm
Re: Main Panel and Sub Panel questions and the NEC March 31, 2008, 2:34 pm
200 amp main panel with 100 amp breaker May 27, 2008, 8:39 am
Main Panel alive with breakers off? August 5, 2005, 4:30 pm
Seeking Advice - New Main Breaker & Sub-Panel January 7, 2006, 9:01 am
Main Disconnect needed for electrical panel? September 7, 2007, 8:59 am
200 amp main cabinet with 100 amp main breaker? March 24, 2006, 6:46 pm
Clog in main sewer line or drain lines running to main line. May 30, 2007, 4:10 pm
Amalgamated Electrci Panel 200-4340 Combo Panel - interior replacement January 6, 2007, 11:16 pm

Contact Us | Privacy Policy

XML SitemapXML Sitemap