Posted by Ian on February 12, 2007, 12:20 pm
Last week woke up and the downstairs main heating zone was not
heating. A second zone feading just 1 room was working and floors 2 &
3 (separate zones) had heat also.
The pipe run actually goes from the furnace, along the wall of the
dining room to the living room where it's baseboard heat, to the
closet, where it's bare insulated pipe, back down the opposite wall of
the living room as baseboard to the addition, where it runs
underground, pops up into a radiator, in the furthest room, then on
the return hits another radiator in the addition, then back
underground to the dining room and another radiator then back to the
furnace.
I know this is a riduclously long run, all told probably atleast 120ft
(living room is 25ft long alone)
Rented the pipe dethawer "Hot Shot 300" and spent the better part of a
day with this puppy clamped to all possible combinations of pipe.
Finally called a plumber who spent 3 hours the next day with the same
machine doing the same thing, before it got to 5 where he stated time
and a half. He suggested we try and get these rooms above 75 degrees
for 48 hours. I've had the further most addition room accidentally up
to104 degrees with a 'jet' LP heater but haven't had the temperature
drop below 55 degrees for 3 days (at night we just leave electric
radiators on).
The circulator is running and I'm able to bleed all radiators, can the
pipes possibly still be frozen? At night it's been down to 5 degrees.
We're on concrete slab, so no basement but I have an electric radiator
sitting on the concrete in the general area between the original house
and the addition where the pipes run underground (in the middle of
some rennovation also).
Any ideas on what else to try would be much appreciated.
thanks
Ian
|
|
Posted by Doug Miller on February 12, 2007, 1:06 pm
show/hide quoted text
>Last week woke up and the downstairs main heating zone was not
>heating. A second zone feading just 1 room was working and floors 2 &
>3 (separate zones) had heat also.
[snip]
show/hide quoted text
>The circulator is running and I'm able to bleed all radiators, can the
>pipes possibly still be frozen?
It's hard to see how.
show/hide quoted text
>At night it's been down to 5 degrees.
>We're on concrete slab, so no basement but I have an electric radiator
>sitting on the concrete in the general area between the original house
>and the addition where the pipes run underground (in the middle of
>some rennovation also).
>Any ideas on what else to try would be much appreciated.
Defective thermostat, defective zone valve, defective wiring, defective
circulator relay, major water leak -- that's about it. :-)
You haven't posted enough information to narrow it down any better than that.
How many circulators in the system? Just one, or does this zone have its own,
dedicated circulator? Presumably, there's a zone valve somewhere, to control
water flow into the zone -- what type? Does it work? Have you tried swapping a
thermostat in from one of the zones that has heat? Have you used a voltmeter
to verify proper voltages at the thermostat, zone valve, and circulator relay?
--
Regards,
Doug Miller (alphageek at milmac dot com)
It's time to throw all their damned tea in the harbor again.
|
|
Posted by Pete C. on February 12, 2007, 1:23 pm
Doug Miller wrote:
show/hide quoted text
>
> >Last week woke up and the downstairs main heating zone was not
> >heating. A second zone feading just 1 room was working and floors 2 &
> >3 (separate zones) had heat also.
> [snip]
> >The circulator is running and I'm able to bleed all radiators, can the
> >pipes possibly still be frozen?
>
> It's hard to see how.
>
> >At night it's been down to 5 degrees.
> >We're on concrete slab, so no basement but I have an electric radiator
> >sitting on the concrete in the general area between the original house
> >and the addition where the pipes run underground (in the middle of
> >some rennovation also).
> >Any ideas on what else to try would be much appreciated.
>
> Defective thermostat, defective zone valve, defective wiring, defective
> circulator relay, major water leak -- that's about it. :-)
>
> You haven't posted enough information to narrow it down any better than that.
> How many circulators in the system? Just one, or does this zone have its own,
> dedicated circulator? Presumably, there's a zone valve somewhere, to control
> water flow into the zone -- what type? Does it work? Have you tried swapping a
> thermostat in from one of the zones that has heat? Have you used a voltmeter
> to verify proper voltages at the thermostat, zone valve, and circulator relay?
>
> --
> Regards,
> Doug Miller (alphageek at milmac dot com)
>
> It's time to throw all their damned tea in the harbor again.
Second on the zone valve. They seem to have a fairly high failure rate
and should be among the first few things to check. They usually have a
manual override lever on them as well so you can still get them opened
when they fail.
|
|
Posted by Ian on February 12, 2007, 2:48 pm
OK, within minutes of actually posting my wife called to tell me the
heat started working, thanks for all the good karma or whatever it
was.
Anyway, to fill in the blanks, not that it matters much now. All zones
have their own circulators. Didn't do any testing with the thermostat
it was still controlling the heat (when I turned it up the circulator
would come on and likewise when I dropped it, it would turn off).
Thanks for the heads up on the failing valves, I'll keep that in mind
for the future. Sorry for not providing enough info. I was 'spoilt'
with a simple hot air system in my previous house. This one is a total
rats nest of pipes going every which way, that I'm still getting to
grips with. Although it's a heck of a lot better than a hot air system
IMHO
Ian
show/hide quoted text
> Doug Miller wrote:
> > >Last week woke up and the downstairs main heating zone was not
> > >heating. A second zone feading just 1 room was working and floors 2 &
> > >3 (separate zones) had heat also.
> > [snip]
> > >The circulator is running and I'm able to bleed all radiators, can the
> > >pipes possibly still be frozen?
> > It's hard to see how.
> > >At night it's been down to 5 degrees.
> > >We're on concrete slab, so no basement but I have an electric radiator
> > >sitting on the concrete in the general area between the original house
> > >and the addition where the pipes run underground (in the middle of
> > >some rennovation also).
> > >Any ideas on what else to try would be much appreciated.
> > Defective thermostat, defective zone valve, defective wiring, defective
> > circulator relay, major water leak -- that's about it. :-)
> > You haven't posted enough information to narrow it down any better than that.
> > How many circulators in the system? Just one, or does this zone have its own,
> > dedicated circulator? Presumably, there's a zone valve somewhere, to control
> > water flow into the zone -- what type? Does it work? Have you tried swapping
a
show/hide quoted text
> > thermostat in from one of the zones that has heat? Have you used a voltmeter
> > to verify proper voltages at the thermostat, zone valve, and circulator
relay?
show/hide quoted text
> > --
> > Regards,
> > Doug Miller (alphageek at milmac dot com)
> > It's time to throw all their damned tea in the harbor again.
> Second on the zone valve. They seem to have a fairly high failure rate
> and should be among the first few things to check. They usually have a
> manual override lever on them as well so you can still get them opened
> when they fail.- Hide quoted text -
> - Show quoted text -
|
| Similar Threads | Posted | | Frozen Pipes Follow up.. | April 27, 2007, 9:56 pm |
| frozen pipes acting weird | January 17, 2007, 4:45 pm |
| Preventing frozen pipes on slab | January 20, 2009, 10:44 pm |
| Floor insulation ==> frozen pipes??? | October 5, 2009, 4:34 pm |
| Frozen Pipes; Heat Tape vs Low Energy, Low Flow, Adjustable Low Temp Redytemp | February 6, 2007, 12:25 pm |
| Repurposing an old blower motor for a grain mill | October 7, 2008, 12:29 am |
| Pipes get jolted: is it a problem? | April 21, 2008, 4:01 am |
| Tree roots in drain pipes - persistent problem? | February 9, 2008, 6:39 pm |
| Septic Frozen? | December 18, 2005, 2:53 am |
| Frozen padlock | January 18, 2006, 6:22 pm |
|
|
>heating. A second zone feading just 1 room was working and floors 2 &
>3 (separate zones) had heat also.