Posted by Dimitrios Paskoudniakis on January 18, 2008, 7:46 pm
> My furnace doesn't seem to start when the thermostat calls for it to
> start. Sometimes it does, sometimes it doesn't. When I place a meter
> across the thermostat terminals (T to T) on the controller (Honeywell
> R8184G1286) the Beckett AF burner starts and runs for several
> cycles...perhaps a week's worth but then won't start until I touch my
> meter probes to the T-T terminals the next time.
>
> Any thoughts would be appreciated.
>
> Boden
I had exactly that problem a few weeks ago. After FOUR trips out by the
HVAC company, replacing the controller (in the furnace) solved it.
At first they replaced a flame sensor, then rewired the power vent, but
these did not solve the problem until they replaced the controller.
|