Home Page link

Outlet in the middle of the floor

Home Repair - - If it ain't broken, don't fix it. Otherwise look here. 

Page 1 of 4       1 2 3 > last >> Bookmark this page:  YahooMyWeb Yahoo!  Google Google  Windows Live Favorites Windows Live  del.icio.us del.icio.us  digg digg  Add to Netscape Netscape
Subject Author Date
Outlet in the middle of the floor MiamiCuse 04-26-2008
If you were  Registered and logged in, you could reply and use other advanced thread options
Posted by MiamiCuse on April 26, 2008, 9:23 pm
I am thinking of custom making a large table (about 120" long by 48" wide)
in the dinning room that will actually protrude about 1/3 of it into the
kitchen. One end of it will serve as an extra island counter for the
kitchen. Since this table will be in the middle of the space, I think I
will need an outlet in case I want to plug in and charge a cell phone, or
plug in a laptop to work on things, may be a juicer etc...

Only problem is the floor is a 4" thick concrete slab and the nearest wall
is 12 feet 2 inches away from the proposed outlet location.

I am not too excited about trenching 12 feet of concrete to put in a PVC
pipe for underground wiring, but I don't think there is another way around
it. I have seen some very flat 12/2 cables that are rated for outdoor UG
use but I am not sure. I will be using stone tiles in the kitchen and those
flat cables may be a possibility but I don't know if that is a good idea.

Another option is to go from the top, then put in a decorative pole from
ceiling to floor punching through the table and the wires go inside, I could
even do phone and cat5 cables in it too.

Thoughts?

MC



Posted by James on April 26, 2008, 10:19 pm
Hmmmmmm......... i am not a contractor or much of a handyman, so this may be
silly, but.........

Instead of thinking about cutting through 4 inches of concrete and laying
pvc pipe down, why can't you rent a concrete cutter and just cut a 1/2
inch slit in the concrete, sufficient to lay down UG wire (or whatever
would meet the code) into the slit ??

Any reason why this would not work ?

James



Posted by Robert Allison on April 26, 2008, 10:29 pm
James wrote:

> Hmmmmmm......... i am not a contractor or much of a handyman, so this may be
> silly, but.........
>
> Instead of thinking about cutting through 4 inches of concrete and laying
> pvc pipe down, why can't you rent a concrete cutter and just cut a 1/2
> inch slit in the concrete, sufficient to lay down UG wire (or whatever
> would meet the code) into the slit ??
>
> Any reason why this would not work ?
>
> James
>
>

It would work, but it is not to code. Any wiring (with the one
notable exception of grounding cable) in concrete must be in a
conduit.

--
Robert Allison
Rimshot, Inc.
Georgetown, TX

Posted by James on April 26, 2008, 10:47 pm

Hmmmmmm. good point Robert. So, could the slit idea still be followed,
but simply be large enough to accomodate the metal conduit ?

James



Posted by Robert Allison on April 27, 2008, 10:57 am
James wrote:

> Hmmmmmm. good point Robert. So, could the slit idea still be followed,
> but simply be large enough to accomodate the metal conduit ?
>
> James
>
>

Absolutely. One would need to go deep enough to accomodate the
90s, but that is how it is done. The conduit can stop just out
of the concrete. I would go with pvc conduit instead of metal.

--
Robert Allison
Rimshot, Inc.
Georgetown, TX

Page 1 of 4       1 2 3 > last >>
Similar ThreadsPosted
Adding an outlet in the middle of an existing circuit? January 9, 2006, 10:35 am
putting an outlet in a ceramic tile floor December 1, 2005, 10:33 pm
chalk line/middle of room November 21, 2005, 3:15 pm
Need Handyman Services in Middle Tennessee? June 15, 2007, 12:18 pm
Suggestions for a 8 foot curtain rod without middle supports January 15, 2008, 7:10 am
Copy of question re switched 230 volt Middle eastern outlets May 3, 2007, 5:00 am
Re: Piggy-backing new 125v outlet on existing 250v outlet? August 9, 2005, 2:28 pm
is gfci outlet good replacement for two-prong non-grounded outlet ?? December 4, 2006, 12:26 pm
8-outlet tap for double-duplex outlet? November 19, 2007, 8:02 am
Vinyl Floor and Standing Shower, damaged floor edge February 20, 2006, 12:01 am

Contact Us | Privacy Policy

XML SitemapXML Sitemap