Quiet condensate pump for gas furnace

Home Repair - - If it ain't broken, don't fix it. Otherwise look here. 

Bookmark this page:  YahooMyWeb Yahoo!  Google Google  Windows Live Favorites Windows Live  del.icio.us del.icio.us  digg digg  Add to Netscape Netscape
Subject Author Date
Quiet condensate pump for gas furnace macmover 06-21-2006
If you were  Registered and logged in, you could reply and use other advanced thread options
Posted by on June 21, 2006, 11:08 pm
The house I just moved into has a closet furnace with a Hartell
KN-20X-1UL condensate pump. I can understand why they felt the need to
pump the water up to the attic and out the side. Finding a way for it
to drain would seem very difficult from the closet. Guess they could
have gone with an furnace installation in the attic but oh well.

However, the thing is noisy. Not so much while the AC is on but after
it's off since condensation can still drip into the pump for up to an
hour or more. At night this has a tendancy to be loud when no other
sound is made.

So I'm wondering if anybody has any advice to a quieter one. The
installer could have gone with a 15' unit instead. It doesn't have to
pump that high. Would a Hartell KN-15X-1UL naturally be quieter because
of this? Thanks.


Posted by Speedy Jim on June 22, 2006, 1:09 pm
macmover@gmail.com wrote:
> The house I just moved into has a closet furnace with a Hartell
> KN-20X-1UL condensate pump. I can understand why they felt the need to
> pump the water up to the attic and out the side. Finding a way for it
> to drain would seem very difficult from the closet. Guess they could
> have gone with an furnace installation in the attic but oh well.
>
> However, the thing is noisy. Not so much while the AC is on but after
> it's off since condensation can still drip into the pump for up to an
> hour or more. At night this has a tendancy to be loud when no other
> sound is made.
>
> So I'm wondering if anybody has any advice to a quieter one. The
> installer could have gone with a 15' unit instead. It doesn't have to
> pump that high. Would a Hartell KN-15X-1UL naturally be quieter because
> of this? Thanks.
>

How about this:

Wire a 24V relay to the compressor contactor leads (at the furnace).
Relay only allows pump to run when compressor is on.
Do an experiment first to be sure the residual condensate won't
overflow the pump tank.

If the furnace is a hi-eff condensing model, it can be configured
the same way during heat season.

Jim

Similar ThreadsPosted
Condensate pump -- please help! May 23, 2007, 3:25 pm
basement dehumidifier, condensate pump March 14, 2006, 2:42 pm
How to quiet a Loud Furnace? January 7, 2008, 8:50 pm
seeking supplier for small quiet electric pump April 23, 2008, 12:13 am
Geothermal heat pump condensate problem. August 4, 2006, 9:15 am
Busted furnace condensate drain trap November 7, 2006, 5:52 pm
New Condensate Pump, add one of those ammonia hocky puck things you use in toilet tanks? December 6, 2005, 9:53 am
Furnace condensate draining directly to crawl space dirt floor January 9, 2007, 1:40 pm
Are quiet bathroom fans really quiet or is it my installation? December 25, 2006, 10:55 am
Furnace vs. Heat Pump December 7, 2006, 1:44 am

Contact Us | Privacy Policy

XML SitemapXML Sitemap