Posted by Wayne Whitney on March 31, 2008, 2:34 pm
> Sure, the fuse disconnect from the meter was replaced by circuit
> breakers, but the sub panels themselves have no main, lugs only. So
> the circuit goes from the main panel breaker to the sub lug only.
> Just curious if the replacements subs need mains or main lugs are
> fine as a replacement....
Main lugs are fine at the subpanel as long as the feeder is protected
at its source by a circuit breaker sized to its wire size. Perhaps
you could provide a small diagram of the service conductors, the
meter, the disconnect, the breakers, and the feeders?
Cheers, Wayne
|
|
Posted by Guy Noir on March 31, 2008, 3:02 pm
>
> > Sure, the fuse disconnect from the meter was replaced by circuit
> > breakers, but the sub panels themselves have no main, lugs only. So
> > the circuit goes from the main panel breaker to the sub lug only.
> > Just curious if the replacements subs need mains or main lugs are
> > fine as a replacement....
>
> Main lugs are fine at the subpanel as long as the feeder is protected
> at its source by a circuit breaker sized to its wire size. =A0Perhaps
> you could provide a small diagram of the service conductors, the
> meter, the disconnect, the breakers, and the feeders?
>
> Cheers, Wayne
Sure enough Wayne.
-----Line from pole-----meter------Main Panel Lugs only------55 Amp
Breaker in Main Panel---------Sub Panel 1 Lugs only
|
|
--------55 Amp Breaker in Main Panel---------Sub Panel 2 Lugs only
Another question, I guess, is what is the max sub panel feed I can
have and not need a Main Breaker installed in the main panel. Or, is
there a cummulative load that would require the addition of a Main
Breaker; like if I add a 3rd panel on a 3rd 55amp breaker.
TIA!
-A
|
|
Posted by Guy Noir on March 31, 2008, 4:46 pm
>
>
> > > Sure, the fuse disconnect from the meter was replaced by circuit
> > > breakers, but the sub panels themselves have no main, lugs only. So
> > > the circuit goes from the main panel breaker to the sub lug only.
> > > Just curious if the replacements subs need mains or main lugs are
> > > fine as a replacement....
>
> > Main lugs are fine at the subpanel as long as the feeder is protected
> > at its source by a circuit breaker sized to its wire size. =A0Perhaps
> > you could provide a small diagram of the service conductors, the
> > meter, the disconnect, the breakers, and the feeders?
>
> > Cheers, Wayne
>
> Sure enough Wayne.
>
> -----Line from pole-----meter------Main Panel Lugs only------55 Amp
> Breaker in Main Panel---------Sub Panel 1 Lugs only
>
> |
>
> |
>
> --------55 Amp Breaker in Main Panel---------Sub Panel 2 Lugs only
>
> Another question, I guess, is what is the max sub panel feed I can
> have and not need a Main Breaker installed in the main panel. Or, is
> there a cummulative load that would require the addition of a Main
> Breaker; like if I add a 3rd panel on a 3rd 55amp breaker.
>
> TIA!
> -A
Further reading indicates that if the Main Panel exceeeds 6 circuits/
Breakers, a main disconnect will be needed. Does a 220 (2 spaces)
count as 1 circuit/breaker?
|
|
Posted by RBM on March 31, 2008, 5:04 pm
>
>
> > > Sure, the fuse disconnect from the meter was replaced by circuit
> > > breakers, but the sub panels themselves have no main, lugs only. So
> > > the circuit goes from the main panel breaker to the sub lug only.
> > > Just curious if the replacements subs need mains or main lugs are
> > > fine as a replacement....
>
> > Main lugs are fine at the subpanel as long as the feeder is protected
> > at its source by a circuit breaker sized to its wire size. Perhaps
> > you could provide a small diagram of the service conductors, the
> > meter, the disconnect, the breakers, and the feeders?
>
> > Cheers, Wayne
>
> Sure enough Wayne.
>
> -----Line from pole-----meter------Main Panel Lugs only------55 Amp
> Breaker in Main Panel---------Sub Panel 1 Lugs only
>
> |
>
> |
>
> --------55 Amp Breaker in Main Panel---------Sub Panel 2 Lugs only
>
> Another question, I guess, is what is the max sub panel feed I can
> have and not need a Main Breaker installed in the main panel. Or, is
> there a cummulative load that would require the addition of a Main
> Breaker; like if I add a 3rd panel on a 3rd 55amp breaker.
>
> TIA!
> -A
Further reading indicates that if the Main Panel exceeeds 6 circuits/
Breakers, a main disconnect will be needed. Does a 220 (2 spaces)
count as 1 circuit/breaker?
One handle, regardless if single or double, is one disconnect
|
|
Posted by RBM on March 31, 2008, 4:56 pm
>
> > Sure, the fuse disconnect from the meter was replaced by circuit
> > breakers, but the sub panels themselves have no main, lugs only. So
> > the circuit goes from the main panel breaker to the sub lug only.
> > Just curious if the replacements subs need mains or main lugs are
> > fine as a replacement....
>
> Main lugs are fine at the subpanel as long as the feeder is protected
> at its source by a circuit breaker sized to its wire size. Perhaps
> you could provide a small diagram of the service conductors, the
> meter, the disconnect, the breakers, and the feeders?
>
> Cheers, Wayne
Sure enough Wayne.
-----Line from pole-----meter------Main Panel Lugs only------55 Amp
Breaker in Main Panel---------Sub Panel 1 Lugs only
|
|
--------55 Amp Breaker in Main Panel---------Sub Panel 2 Lugs only
Another question, I guess, is what is the max sub panel feed I can
have and not need a Main Breaker installed in the main panel. Or, is
there a cummulative load that would require the addition of a Main
Breaker; like if I add a 3rd panel on a 3rd 55amp breaker.
TIA!
-A
If there is not a 200 amp disconnect at the meter equipment, you are limited
to six disconnects in or at the main panel. The sub panels do not need
disconnects in them unless they are in separate buildings, garages, out
buildings, etc, but if the main panel is larger than what will hold 6-
double pole breakers, you need a main disconnect to use those spaces
|
| Similar Threads | Posted | | Main Panel and Sub Panel questions and the NEC | March 31, 2008, 1:48 pm |
| Main panel to main panel wiring in converting multi-family to single family dwelling | November 9, 2006, 6:35 pm |
| New Main Panel Help | April 11, 2008, 2:04 pm |
| 200 amp main panel with 100 amp breaker | May 27, 2008, 8:39 am |
| Main Panel alive with breakers off? | August 5, 2005, 4:30 pm |
| Seeking Advice - New Main Breaker & Sub-Panel | January 7, 2006, 9:01 am |
| Main Disconnect needed for electrical panel? | September 7, 2007, 8:59 am |
| Amalgamated Electrci Panel 200-4340 Combo Panel - interior replacement | January 6, 2007, 11:16 pm |
| 2nd panel running off of primary electrical panel | December 17, 2006, 9:12 pm |
| Electrical sub-panel questions | September 24, 2005, 11:15 am |
|
|