Posted by Wayne Whitney on January 28, 2008, 1:01 pm
> While there is a change in the 2008 NEC regarding multi-wire branch
> circuits (MWBCs), it does not make them illegal. In the 2005 NEC,
> if the MWBC served a single yoke with multiple devices, then a means
> of disconnecting both legs simultaneously is required. In the 2008
> NEC, this is always required. The practical implication for
> residential work is that you have use a double pole breaker.
That should say that you have to use a double pole breaker with handle
tie.
Cheers, Wayne
|