Posted by Wayne Whitney on February 3, 2008, 9:28 pm

> 12 guage wire on a 30A breaker a code violation and can be fire
> hazard.

This is 98% true. The one exception I know of is for motor loads.
Motors can have a very high startup current, so in a dedicated motor
circuit an alternate arrangement is acceptable, as follows. The motor
itself or a dedicated motor controller or relay provides the
overcurrent (overload) protection. The breaker is just for short
circuit/ground fault protection. The breaker is sized so that it
doesn't trip due to the startup current. So you could end up with a
30 amp breaker on a #12 wire. For further details, see Article 430 of
the NEC.

Cheers, Wayne



Similar ThreadsPosted
why common trip breakers for 120V circuits? February 3, 2008, 6:26 pm
Re: why common trip breakers for 120V circuits? February 3, 2008, 9:24 pm
changing 240v trip on circuit breaker to 120v November 5, 2007, 7:15 pm
breakers don't trip, electricity out November 25, 2007, 1:12 am
Re: Do circuit breakers hallucinate when they trip? November 18, 2008, 4:28 am
Re: Do circuit breakers hallucinate when they trip? November 18, 2008, 8:48 am
Re: Do circuit breakers hallucinate when they trip? November 19, 2008, 1:12 pm
Re: Do circuit breakers hallucinate when they trip? November 20, 2008, 8:28 pm
Re: Do circuit breakers hallucinate when they trip? November 20, 2008, 9:16 pm
How Common Was This? September 25, 2008, 3:50 pm

Contact Us | Privacy Policy

XML SitemapXML Sitemap