Remodeling upstairs condo, power out downstairs condo

Home Repair - - If it ain't broken, don't fix it. Otherwise look here. 

Page 1 of 2       1 2 > last >> Bookmark this page:  YahooMyWeb Yahoo!  Google Google  Windows Live Favorites Windows Live  del.icio.us del.icio.us  digg digg  Add to Netscape Netscape
Subject Author Date
Remodeling upstairs condo, power out downstairs condo Norminn 06-27-2007
If you were  Registered and logged in, you could reply and use other advanced thread options
Posted by Norminn on June 27, 2007, 5:05 pm
Arggggghhhhh! New owner of condo above ours has gutted his kitchen and
is putting down Pergo-type flooring in other rooms. We began having
trouble with one or another electrical circuits going out in our condo
whilst he worked upstairs. The first time, he was hammering almost
above where I was sitting and at the same moment, power went out in our
dining room and adjoining office area. Went out and reset the breaker,
aok. Then, twice, the elec. to our two baths and small hallway went
out. I didn't notice when it happened, as I don't use those lights
during the day. We reset the breaker once, and aok, but reset the
breaker next time and now the power won't come on to the baths and
hallway. The guy wasn't truthful, I believe, when he told me he was
working in a different area the first time it happened. I haven't seen
his condo, but hubby said kitchen is gutted to the studs with wires
hanging all over. He allegedly has an electrician. His unit is same
layout as ours, but entirely separate breaker panels. I assume much of
our wiring would be beneath his floor.

I have called the city building dept, no response yet, and fire insp.,
not their job. I think he must have put a nail through a wire, but I
don't know electricity or breaker panels or ohms or watts. Can the
vibration from his work wiggle something loose in the main panel? Any
other ideas? My dryer is broken, waiting for a part, and I can't handle
this much stress all at once :o)

Posted by William Underhill on June 27, 2007, 7:16 pm
Norminn wrote:
> Arggggghhhhh! New owner of condo above ours has gutted his kitchen and
> is putting down Pergo-type flooring in other rooms. We began having
> trouble with one or another electrical circuits going out in our condo
> whilst he worked upstairs. The first time, he was hammering almost
> above where I was sitting and at the same moment, power went out in our
> dining room and adjoining office area. Went out and reset the breaker,
> aok. Then, twice, the elec. to our two baths and small hallway went
> out. I didn't notice when it happened, as I don't use those lights
> during the day. We reset the breaker once, and aok, but reset the
> breaker next time and now the power won't come on to the baths and
> hallway. The guy wasn't truthful, I believe, when he told me he was
> working in a different area the first time it happened. I haven't seen
> his condo, but hubby said kitchen is gutted to the studs with wires
> hanging all over. He allegedly has an electrician. His unit is same
> layout as ours, but entirely separate breaker panels. I assume much of
> our wiring would be beneath his floor.
>
> I have called the city building dept, no response yet, and fire insp.,
> not their job. I think he must have put a nail through a wire, but I
> don't know electricity or breaker panels or ohms or watts. Can the
> vibration from his work wiggle something loose in the main panel? Any
> other ideas? My dryer is broken, waiting for a part, and I can't handle
> this much stress all at once :o)

Vibration isn't likely to 'wiggle' anything loose, but I agree that it's
entirely possible he's put a nail through a wire belonging to you. If
your unit is partly sub-grade probably most of the horizontal runs of
your wiring goes through your ceiling/his floor.

Did he run his proposed renovations past your strata council? Generally
that's pretty much a requirement. If not, go to your strata council and
explain what's happening. I'm also pretty sure he needs permits from the
city to be doing work or having work done, and things need to be
inspected afterward. This character may be trying to slide his
renovations in 'under the radar'.

Yours aye,
W. Underhill

--
"Take sides! Always take sides! You may sometimes be wrong - but the man
who refuses to take sides must *always* be wrong! Heaven save us from
poltroons who fear to make a choice!" R.A. Heinlein, "Double Star"
--
Main homepage: http://members.shaw.ca/fog.locker/
SCA homepage: http://members.shaw.ca/uilliam/
LiveJournal: http://www.livejournal.com/users/jackytar/

Posted by Tony Hwang on June 27, 2007, 9:20 pm
Norminn wrote:
> Arggggghhhhh! New owner of condo above ours has gutted his kitchen and
> is putting down Pergo-type flooring in other rooms. We began having
> trouble with one or another electrical circuits going out in our condo
> whilst he worked upstairs. The first time, he was hammering almost
> above where I was sitting and at the same moment, power went out in our
> dining room and adjoining office area. Went out and reset the breaker,
> aok. Then, twice, the elec. to our two baths and small hallway went
> out. I didn't notice when it happened, as I don't use those lights
> during the day. We reset the breaker once, and aok, but reset the
> breaker next time and now the power won't come on to the baths and
> hallway. The guy wasn't truthful, I believe, when he told me he was
> working in a different area the first time it happened. I haven't seen
> his condo, but hubby said kitchen is gutted to the studs with wires
> hanging all over. He allegedly has an electrician. His unit is same
> layout as ours, but entirely separate breaker panels. I assume much of
> our wiring would be beneath his floor.
>
> I have called the city building dept, no response yet, and fire insp.,
> not their job. I think he must have put a nail through a wire, but I
> don't know electricity or breaker panels or ohms or watts. Can the
> vibration from his work wiggle something loose in the main panel? Any
> other ideas? My dryer is broken, waiting for a part, and I can't handle
> this much stress all at once :o)
Hi,
Talk to condo manager or raise the issue with condo board.

Posted by Norminn on June 29, 2007, 9:45 pm
Tony Hwang wrote:
> Norminn wrote:
>
>> Arggggghhhhh! New owner of condo above ours has gutted his kitchen
>> and is putting down Pergo-type flooring in other rooms. We began
>> having trouble with one or another electrical circuits going out in
>> our condo whilst he worked upstairs. The first time, he was hammering
>> almost above where I was sitting and at the same moment, power went
>> out in our dining room and adjoining office area. Went out and reset
>> the breaker, aok. Then, twice, the elec. to our two baths and small
>> hallway went out. I didn't notice when it happened, as I don't use
>> those lights during the day. We reset the breaker once, and aok, but
>> reset the breaker next time and now the power won't come on to the
>> baths and hallway. The guy wasn't truthful, I believe, when he told
>> me he was working in a different area the first time it happened. I
>> haven't seen his condo, but hubby said kitchen is gutted to the studs
>> with wires hanging all over. He allegedly has an electrician. His
>> unit is same layout as ours, but entirely separate breaker panels. I
>> assume much of our wiring would be beneath his floor.
>>
>> I have called the city building dept, no response yet, and fire insp.,
>> not their job. I think he must have put a nail through a wire, but I
>> don't know electricity or breaker panels or ohms or watts. Can the
>> vibration from his work wiggle something loose in the main panel? Any
>> other ideas? My dryer is broken, waiting for a part, and I can't
>> handle this much stress all at once :o)
>
> Hi,
> Talk to condo manager or raise the issue with condo board.
We have only 8 units in our condo. Two owned by lush deadbeats,
father and son. Son is months behind on monthly assessment and hasn't
begun to pay a $2200 special assessment. Condo pres. is best buddies
with them. Did I mention the father and son are both on the board? The
father had a million-dollar sailboat, lives here part-time....home in
the Bahamas. Unfortunately, he appears to be in good health. A lien?
Not much good, unless one of them croaks. One unit owner lives in
England, one in Jersey. The neighbor who wrecked my wiring told me he
has a likely buyer...owned his unit since March.

Posted by Norminn on June 29, 2007, 4:46 pm
Norminn wrote:
> Arggggghhhhh! New owner of condo above ours has gutted his kitchen and
> is putting down Pergo-type flooring in other rooms. We began having
> trouble with one or another electrical circuits going out in our condo
> whilst he worked upstairs. The first time, he was hammering almost
> above where I was sitting and at the same moment, power went out in our
> dining room and adjoining office area. Went out and reset the breaker,
> aok. Then, twice, the elec. to our two baths and small hallway went
> out. I didn't notice when it happened, as I don't use those lights
> during the day. We reset the breaker once, and aok, but reset the
> breaker next time and now the power won't come on to the baths and
> hallway. The guy wasn't truthful, I believe, when he told me he was
> working in a different area the first time it happened. I haven't seen
> his condo, but hubby said kitchen is gutted to the studs with wires
> hanging all over. He allegedly has an electrician. His unit is same
> layout as ours, but entirely separate breaker panels. I assume much of
> our wiring would be beneath his floor.
>
> I have called the city building dept, no response yet, and fire insp.,
> not their job. I think he must have put a nail through a wire, but I
> don't know electricity or breaker panels or ohms or watts. Can the
> vibration from his work wiggle something loose in the main panel? Any
> other ideas? My dryer is broken, waiting for a part, and I can't handle
> this much stress all at once :o)

Well, the electricians just left. It's Friday. They knew immediately
what the problem was......nails through the pipe and wire, multiple
times through one length of wire. Wires burned through entirely. Might
be back tomorrow - overtime, have to check with the office. They can't
get wires fed through the pipe, so may have to replace it. It would be
easier to tear out my flawless ceiling than to tear up my idiot
neighbor's floor........The electrician said there had to have been
sparks when the neighbor hit the nails. I have the building department
coming back Monday because the neighbor told him a different story than
he told me about doing structural work. I don't like idiots or liars.
At least the part for my dryer is in....can't wait 'til Monday.

Why are all the idiots on the planet moving into my condo?

And thanks to all who offered assistance. I appreciate it.

Page 1 of 2       1 2 > last >>
Similar ThreadsPosted
Warmer upstairs vs. downstairs May 29, 2006, 10:44 pm
Hot upstairs cool downstairs July 9, 2007, 12:19 am
Flushing downstairs causes dripping upstairs? June 2, 2008, 10:28 am
A/C for my condo July 5, 2005, 12:21 pm
Condo floors November 7, 2006, 12:11 am
Help with condo electric problem April 29, 2006, 9:17 pm
Hard water in condo June 21, 2006, 7:54 am
soundproofing condo door September 15, 2006, 11:30 am
CONDO BATH TUB SHOWER BAR March 30, 2007, 2:15 am
Air leaks normal in new condo? February 6, 2007, 9:56 pm

Contact Us | Privacy Policy

XML SitemapXML Sitemap