|
Posted by on May 11, 2008, 10:25 am
>
>>
>>>
>>>> There is a boiler in one wing of a home I own that has a tankless water
>>>> heater.
>>>> This wing of the house is closed off and not occupied. I only run the
>>>> boiler
>>>> enough to keep pipes from freezing in winter. I would like to disconnect
>>>> the
>>>> domestic hot water since it sometimes makes the boiler run even though
>>>> there is
>>>> no use for domestic HW in that part of the house. Can I simply cap off
>>>> the
>>>> cold
>>>> water supply to the exchanger, drain it, and forget about it, or do I
>>>> need
>>>> to
>>>> remove the coil?
>>>
>>>You could do any or all of the above, but it won't stop the boiler from
>>>running. The easiest thing to do is shut the power to the boiler when the
>>>heating season is over. The other thing you can do is turn down the
>>>aquastat
>>>that controls the domestic hot water. This is sometimes a separate device
>>>piped into the boiler's water jacket, and on newer boilers it's often a
>>>triple aquastat relay, which will have a low temperature cut in and a high
>>>temperature cutout within one box. In either case, just turn down the cut
>>>in
>>>control as far as it will go, and the boiler shouldn't fire unless a
>>>thermostat calls for heat
>>>>
>>>>
>>>
>>
>> Thanks. Are you saying that turning that control down all the way won't
>> affect
>> the boiler functions of heating of the house? That almost seems too easy.
>> I
>> thought that control would affect the water temp to the baseboard heating
>> circuit as well.
>>
>> I do shut down the boiler as soon as danger of a hard freeze is over. All
>> the
>> upper floor's domestic water plumbing and baseboards are empty, so I only
>> need
>> to heat the basement slightly to avoid damage to the foundation. I'm just
>> trying
>> to save as much oil out there as possible, and don't want to use any oil
>> for
>> heating domestic hot water that nobody needs.
>
>Without knowing the controls you have on the boiler, I can't say for
>certain, but a typical modern boiler equipped with domestic coil, will have
>a triple aquastat relay, and the low temperature cut in is only to maintain
>tank temperature for the coil. The heating thermostat(s) will shunt the "T
>T" terminals in the relay and fire the boiler overriding the low temp cut
>in, and stay fired until the boiler reaches the high limit, or the zone
>calling for heat is satisfied
>>
Thanks very much. The boiler is only a year old, so I imagine the controls are
what you are describing. To be safe, I'll try changing the settings, and wait
around to make sure everyting is okay before walking away from it.
|