Remove tankless HW from boiler? salty 05-11-2008
If you were  Registered and logged in, you could reply and use other advanced thread options
Posted by RBM on May 11, 2008, 10:39 am

>
>>
>>>
>>>>
>>>>> There is a boiler in one wing of a home I own that has a tankless
>>>>> water
>>>>> heater.
>>>>> This wing of the house is closed off and not occupied. I only run the
>>>>> boiler
>>>>> enough to keep pipes from freezing in winter. I would like to
>>>>> disconnect
>>>>> the
>>>>> domestic hot water since it sometimes makes the boiler run even though
>>>>> there is
>>>>> no use for domestic HW in that part of the house. Can I simply cap off
>>>>> the
>>>>> cold
>>>>> water supply to the exchanger, drain it, and forget about it, or do I
>>>>> need
>>>>> to
>>>>> remove the coil?
>>>>
>>>>You could do any or all of the above, but it won't stop the boiler from
>>>>running. The easiest thing to do is shut the power to the boiler when
>>>>the
>>>>heating season is over. The other thing you can do is turn down the
>>>>aquastat
>>>>that controls the domestic hot water. This is sometimes a separate
>>>>device
>>>>piped into the boiler's water jacket, and on newer boilers it's often a
>>>>triple aquastat relay, which will have a low temperature cut in and a
>>>>high
>>>>temperature cutout within one box. In either case, just turn down the
>>>>cut
>>>>in
>>>>control as far as it will go, and the boiler shouldn't fire unless a
>>>>thermostat calls for heat
>>>>>
>>>>>
>>>>
>>>
>>> Thanks. Are you saying that turning that control down all the way won't
>>> affect
>>> the boiler functions of heating of the house? That almost seems too
>>> easy.
>>> I
>>> thought that control would affect the water temp to the baseboard
>>> heating
>>> circuit as well.
>>>
>>> I do shut down the boiler as soon as danger of a hard freeze is over.
>>> All
>>> the
>>> upper floor's domestic water plumbing and baseboards are empty, so I
>>> only
>>> need
>>> to heat the basement slightly to avoid damage to the foundation. I'm
>>> just
>>> trying
>>> to save as much oil out there as possible, and don't want to use any oil
>>> for
>>> heating domestic hot water that nobody needs.
>>
>>Without knowing the controls you have on the boiler, I can't say for
>>certain, but a typical modern boiler equipped with domestic coil, will
>>have
>>a triple aquastat relay, and the low temperature cut in is only to
>>maintain
>>tank temperature for the coil. The heating thermostat(s) will shunt the "T
>>T" terminals in the relay and fire the boiler overriding the low temp cut
>>in, and stay fired until the boiler reaches the high limit, or the zone
>>calling for heat is satisfied
>>>
>
> Thanks very much. The boiler is only a year old, so I imagine the controls
> are
> what you are describing. To be safe, I'll try changing the settings, and
> wait
> around to make sure everyting is okay before walking away from it.

All you have to do is turn the low temp cut in all the way down, then turn a
heating thermostat up and the boiler should fire, unless the tank
temperature is already at the limit, in which case it'll fire after some hot
water circulates, dropping it's temperature
>
>



Posted by hallerb@aol.com on May 11, 2008, 11:18 am
so you have a one year old boiler heating just barely to keep above
freezing a unused space??

i would ask a heating contractor for the option of using the primary
boiler to heat the unused space, thru a zone control.

this woulds shut down the second boiler entirely and may well cost
less.

it could be plumbed by changing some valves to put the secondary
boiler back on line someday.

plus theres no maintence on a unused boiler

Page 2 of 2       << first < 1 2
Similar ThreadsPosted
tankless boiler efficiency? July 28, 2006, 4:17 pm
tankless water heater/boiler? August 6, 2005, 1:49 pm
Recommendation for Tankless/Condensing Boiler? July 27, 2006, 11:49 am
Tankless boiler not providing enough hot water---help!! June 20, 2007, 2:10 pm
Advice please on how to remove a Cast Iron Back Boiler January 1, 2006, 8:01 pm
Help - I have a back boiler and want a combi boiler fitted but have plastic pipes! November 22, 2005, 2:26 pm
boiler question: put in new block assembly or replace boiler? January 4, 2007, 11:36 pm
Conversion Oil fired boiler to Electric boiler May 16, 2007, 10:23 am
how to tell a steam boiler from a hot water boiler May 12, 2006, 12:53 pm
Old boiler to New boiler and water heater March 10, 2008, 9:59 pm

Contact Us | Privacy Policy

XML SitemapXML Sitemap