Req'd to replace small outlet boxes when upgrading wiring in an olderhome?

Home Repair - - If it ain't broken, don't fix it. Otherwise look here. 

Page 2 of 2       << first < 1 2 Bookmark this page:  YahooMyWeb Yahoo!  Google Google  Windows Live Favorites Windows Live  del.icio.us del.icio.us  digg digg  Add to Netscape Netscape
Subject Author Date
Req'd to replace small outlet boxes when upgrading wiring in an olderhome? Himanshu 08-07-2005
If you were  Registered and logged in, you could reply and use other advanced thread options
Posted by on August 7, 2005, 2:11 am


On Sun, 07 Aug 2005 04:39:33 GMT, Himanshu

>I'm upgrading wiring in an older home which originally had ungrounded
>two-wire fabric-sheathed cable. I replaced it with 12/2 with grounding
>wire in a few circuits.
>
>The existing handy boxes (is that the right word for outlet boxes?) are
>not as big as the ones currently being sold.
>
>For a middle of the run receptacle, I'm looking at 4 wires + ground +
>grounding wire nut (the one with the pass through if you've seen them)
>and clamps in one of those boxes which is 12 cu in or less, and I can
>barely close up the outlet cover.
>
>I'm wondering, is it required to change the outlet boxes to the bigger
>14 cu in (or bigger) boxes when I upgrade the wiring? That would be
>much more work than I had originally anticipated.
>
>Thanks.


Short answer is yes. For 12ga, 5 wires and a receptacle you need a 16
cu/in box.


PexSupply Save 10 468x60
Posted by Himanshu on August 9, 2005, 10:46 pm


Himanshu wrote:
> I'm upgrading wiring in an older home which originally had ungrounded
> two-wire fabric-sheathed cable. I replaced it with 12/2 with grounding
> wire in a few circuits.
<snip>
> I'm wondering, is it required to change the outlet boxes to the bigger
> 14 cu in (or bigger) boxes when I upgrade the wiring? That would be
> much more work than I had originally anticipated.

Thank you all for your suggestions.

The local inspector said that for the end-of-the-run, I could keep the
older box, but for middle-of-the-run, I would have to install a bigger
box during the upgrade.

--
Himanshu


Page 2 of 2       << first < 1 2
Similar ThreadsPosted
Upgrading Electrical Outlet August 28, 2008, 12:56 pm
Loose outlet boxes: options January 10, 2007, 5:42 pm
Straight and level outlet boxes January 10, 2007, 7:56 pm
Ok to use outlet boxes larger than required by code? March 5, 2006, 12:38 pm
Electric Outlet Boxes in Vinyl Siding June 21, 2008, 3:10 pm
small 'bulging bay windows' for plants, to replace single hung window,called what? July 19, 2005, 12:57 pm
Small wiring puzzle May 10, 2008, 7:15 pm
I need to replace an outlet for a dryer December 13, 2006, 3:09 pm
Question about wiring 2 light circuits with dimmers in small space February 21, 2007, 11:26 am
Wiring help - replace faulty light switch August 1, 2008, 2:57 am

Contact Us | Privacy Policy

XML SitemapXML Sitemap