Rewire 220v to 110v Color question

Home Repair - - If it ain't broken, don't fix it. Otherwise look here. 

Page 1 of 5       1 2 3 > last >> Bookmark this page:  YahooMyWeb Yahoo!  Google Google  Windows Live Favorites Windows Live  del.icio.us del.icio.us  digg digg  Add to Netscape Netscape
Subject Author Date
Rewire 220v to 110v Color question Guy Noir 07-30-2007
If you were  Registered and logged in, you could reply and use other advanced thread options
Posted by Guy Noir on July 30, 2007, 1:30 pm
Question: I have installed central air and I no longer need to 220v
window AC outlets.

They are wired with romax and the colors of the conductor insulation
are Black, Red, and White.
With the current cost of copper, I hate to replace these runs.

Standard color codes are of course black, white, copper/gnd. If I
rewire this for 110v what colors should I put where? I read somewhere
in the code that you can re-identify a cable with colored tape (green
for instance for the wire used for ground)

So, should I use black-hot white-neutral and red-green taped at each
end for ground? Does this meet NEC code or at least come close??

Thanks in Advance, as always!!

-A


Real Goods Solar, Inc.
Posted by Doug Miller on July 30, 2007, 1:39 pm
>Question: I have installed central air and I no longer need to 220v
>window AC outlets.
>
>They are wired with romax and the colors of the conductor insulation
>are Black, Red, and White.

No bare wire??

>With the current cost of copper, I hate to replace these runs.
>
>Standard color codes are of course black, white, copper/gnd. If I
>rewire this for 110v what colors should I put where? I read somewhere
>in the code that you can re-identify a cable with colored tape (green
>for instance for the wire used for ground)

That is not correct. Grounding conductors larger than 6AWG are permitted to be
re-identified in that manner, but not 6AWG and smaller. [2005 NEC, Article
250.119]
>
>So, should I use black-hot white-neutral and red-green taped at each
>end for ground? Does this meet NEC code or at least come close??

No.

--
Regards,
Doug Miller (alphageek at milmac dot com)

It's time to throw all their damned tea in the harbor again.

Posted by dpb on July 31, 2007, 5:57 pm
Doug Miller wrote:
>> Question: I have installed central air and I no longer need to 220v
>> window AC outlets.
>>
>> They are wired with romax and the colors of the conductor insulation
>> are Black, Red, and White.
>
> No bare wire??
>
>> With the current cost of copper, I hate to replace these runs.
>>
>> Standard color codes are of course black, white, copper/gnd. If I
>> rewire this for 110v what colors should I put where? I read somewhere
>> in the code that you can re-identify a cable with colored tape (green
>> for instance for the wire used for ground)
>
> That is not correct. Grounding conductors larger than 6AWG are permitted to be
> re-identified in that manner, but not 6AWG and smaller. [2005 NEC, Article
> 250.119]
>> So, should I use black-hot white-neutral and red-green taped at each
>> end for ground? Does this meet NEC code or at least come close??
>
> No.

Doesn't meet letter of the code, but I'd not hesitate to do so, myself.
If certainly meets everything but the color and the electrons don't
know the difference. The marking needs to be substantial enough so as
to be relied upon for staying there.

My personal opinion on it is that it is old work, not new and there's no
inspector I've ever seen who wouldn't make reasonable allowance for that...

Others opinions/choices/etc., may differ of course...

--



Posted by John Grabowski on July 30, 2007, 2:07 pm

> Question: I have installed central air and I no longer need to 220v
> window AC outlets.
>
> They are wired with romax and the colors of the conductor insulation
> are Black, Red, and White.
> With the current cost of copper, I hate to replace these runs.
>
> Standard color codes are of course black, white, copper/gnd. If I
> rewire this for 110v what colors should I put where? I read somewhere
> in the code that you can re-identify a cable with colored tape (green
> for instance for the wire used for ground)
>
> So, should I use black-hot white-neutral and red-green taped at each
> end for ground? Does this meet NEC code or at least come close??
>


Yes, you'll be fine. Make sure the green is continuous and no red is
visible. Isn't there an equipment grounding conductor in the box now?



Posted by Guy Noir on July 30, 2007, 2:31 pm
>
>
> > Question: I have installed central air and I no longer need to 220v
> > window AC outlets.
>
> > They are wired with romax and the colors of the conductor insulation
> > are Black, Red, and White.
> > With the current cost of copper, I hate to replace these runs.
>
> > Standard color codes are of course black, white, copper/gnd. If I
> > rewire this for 110v what colors should I put where? I read somewhere
> > in the code that you can re-identify a cable with colored tape (green
> > for instance for the wire used for ground)
>
> > So, should I use black-hot white-neutral and red-green taped at each
> > end for ground? Does this meet NEC code or at least come close??
>
> Yes, you'll be fine. Make sure the green is continuous and no red is
> visible. Isn't there an equipment grounding conductor in the box now?

Unfortunately, no there is no bare or green conductor.

-A



Page 1 of 5       1 2 3 > last >>
Similar ThreadsPosted
NEC question -- can a circuit have both 220v and 110v outlets August 3, 2007, 10:06 am
Question on adding 220V and 110V circuits to garage January 22, 2006, 1:33 am
220V for 110V cooktop? November 2, 2005, 11:46 pm
220v Well Pump on 110v? January 14, 2007, 9:25 pm
How to tell if audio equipment is 110V or 220V? August 5, 2006, 12:51 pm
is it OK to use 110V lamps plugged into 220V outlets??? March 15, 2007, 8:32 am
Electrical - convert 110v to 220v outlet using 12/2 w/ground August 4, 2006, 7:15 pm
110v line to 220v line? January 5, 2006, 6:15 pm
A countertop oven (Jetstream) 110V 60Hz versus 110V 50Hz - problems? November 11, 2006, 4:13 pm
Elec Question-Stove, uwave 220/110V January 30, 2008, 7:13 pm

Contact Us | Privacy Policy

XML SitemapXML Sitemap