|
Posted by RBM on October 29, 2006, 7:10 am
There may be a few other things left out, such as ground conductor, ground
rods, and expansion couplings. Can you not come out of the ground at the
garage and use an LB condulet to go through the siding?
> I'm wiring up my detached garage for 220v/50amps for a TIG Welder and air
> compressor. The plan is to change the breaker in the main panel for the
> 220v/30amp to a dryer outlet that is not being used to a 60amp breaker.
> I'm planning on running some new 6 AWG copper wire, 8 AWG neutral, about
> 75 feet to the garage into a subpanel with a 50amp breaker.
>
> My problem is the routing of the wire. The wire will start out from the
> main breaker, go up to the attic, down another wall, to the outside via a
> 1" Schedule 80 PVC piping. Here it will go into the ground, minimum of 18"
> deep. This is where I get stuck, the outside wall of the garage is
> surrounded by a 3 foot section of concrete. Is it permissible to run the
> PVC on top of the concrete floor to enter the garage wall?
>
> Or is the only way to somehow cut the concrete and lay the pipe?
>
> Thanks in advance!
>
> Darius
>
|