Posted by willshak on June 1, 2006, 9:17 am
Phillip77776666@yahoo.com wrote:
> I'm installing a 20A GFCI receptacle on my 4x4 deck post using the
> proper weather proof box and cover. I plan to run 12-2 UF wire from my
> garage subpanel (about 40ft.) to it, the GFCI outlet will have it's own
> 20A breaker. BTW; The subpanel is on a 50A main breaker using 6/3 with
> ground cable; really doesn't have much on it, other than a 50 gallon
> water heater on a 30A double pole and also garage receptacles, five
> fluorescent strip lights, couple outside wall lights which are on a
> seperate 20A breaker.
>
> But, I'm confused; Do I need to run the wire through conduit? It's not
> going to be close to the ground or anywhere close to where it might get
> damaged. What about when I run the wire through the floor sill (inside
> a wall) of the garage to outside? Do I need to protect the wire? If so,
> could I just run the wire through ordinary short piece of 1/2" CPVC
> pipe? The GFCI outlet is for a pool pump motor, which draws about 13.5
> amps and will be running about 12 hours a day. I don't want to violate
> any NEC codes. Thanks for the help
>
>
Check with your electrical inspector to see what's required in your area.
There are some codes that require an outlet near the pool (so you're not
using extension cords) and how far away from the water it must be.
My pool's 240 v. subpanel is fed from the house's main panel through and
between the basement ceiling joists, then through the sill to an access
junction box, and then down and underground to the pool panel attached
to the side of the pool house. Total distance is about 75'. It is in pvc
pipe the entire distance between the two electrical panels, and was
installed by an electrician and inspected and approved by the electrical
inspector.
All the GFCI breakers are in the pool's subpanel, not the main panel. I
also run the electricity for the pool house from this subpanel.
--
Bill
In Hamptonburgh, NY