Running wire to outside

Home Repair - - If it ain't broken, don't fix it. Otherwise look here. 

Bookmark this page:  YahooMyWeb Yahoo!  Google Google  Windows Live Favorites Windows Live  del.icio.us del.icio.us  digg digg  Add to Netscape Netscape
Subject Author Date
Running wire to outside Phillip77776666 06-01-2006
If you were  Registered and logged in, you could reply and use other advanced thread options
Posted by on June 1, 2006, 6:13 am
I'm installing a 20A GFCI receptacle on my 4x4 deck post using the
proper weather proof box and cover. I plan to run 12-2 UF wire from my
garage subpanel (about 40ft.) to it, the GFCI outlet will have it's own
20A breaker. BTW; The subpanel is on a 50A main breaker using 6/3 with
ground cable; really doesn't have much on it, other than a 50 gallon
water heater on a 30A double pole and also garage receptacles, five
fluorescent strip lights, couple outside wall lights which are on a
seperate 20A breaker.

But, I'm confused; Do I need to run the wire through conduit? It's not
going to be close to the ground or anywhere close to where it might get
damaged. What about when I run the wire through the floor sill (inside
a wall) of the garage to outside? Do I need to protect the wire? If so,
could I just run the wire through ordinary short piece of 1/2" CPVC
pipe? The GFCI outlet is for a pool pump motor, which draws about 13.5
amps and will be running about 12 hours a day. I don't want to violate
any NEC codes. Thanks for the help


Plumbing 468x60
Posted by RBM on June 1, 2006, 6:56 am
You can use UF, and should sleeve it in PVC where subject to physical
damage, however wiring for swimming pools and related equipment carry their
own code requirements depending upon type and size of the pool



> I'm installing a 20A GFCI receptacle on my 4x4 deck post using the
> proper weather proof box and cover. I plan to run 12-2 UF wire from my
> garage subpanel (about 40ft.) to it, the GFCI outlet will have it's own
> 20A breaker. BTW; The subpanel is on a 50A main breaker using 6/3 with
> ground cable; really doesn't have much on it, other than a 50 gallon
> water heater on a 30A double pole and also garage receptacles, five
> fluorescent strip lights, couple outside wall lights which are on a
> seperate 20A breaker.
>
> But, I'm confused; Do I need to run the wire through conduit? It's not
> going to be close to the ground or anywhere close to where it might get
> damaged. What about when I run the wire through the floor sill (inside
> a wall) of the garage to outside? Do I need to protect the wire? If so,
> could I just run the wire through ordinary short piece of 1/2" CPVC
> pipe? The GFCI outlet is for a pool pump motor, which draws about 13.5
> amps and will be running about 12 hours a day. I don't want to violate
> any NEC codes. Thanks for the help
>



Posted by willshak on June 1, 2006, 9:17 am
Phillip77776666@yahoo.com wrote:
> I'm installing a 20A GFCI receptacle on my 4x4 deck post using the
> proper weather proof box and cover. I plan to run 12-2 UF wire from my
> garage subpanel (about 40ft.) to it, the GFCI outlet will have it's own
> 20A breaker. BTW; The subpanel is on a 50A main breaker using 6/3 with
> ground cable; really doesn't have much on it, other than a 50 gallon
> water heater on a 30A double pole and also garage receptacles, five
> fluorescent strip lights, couple outside wall lights which are on a
> seperate 20A breaker.
>
> But, I'm confused; Do I need to run the wire through conduit? It's not
> going to be close to the ground or anywhere close to where it might get
> damaged. What about when I run the wire through the floor sill (inside
> a wall) of the garage to outside? Do I need to protect the wire? If so,
> could I just run the wire through ordinary short piece of 1/2" CPVC
> pipe? The GFCI outlet is for a pool pump motor, which draws about 13.5
> amps and will be running about 12 hours a day. I don't want to violate
> any NEC codes. Thanks for the help
>
>

Check with your electrical inspector to see what's required in your area.
There are some codes that require an outlet near the pool (so you're not
using extension cords) and how far away from the water it must be.
My pool's 240 v. subpanel is fed from the house's main panel through and
between the basement ceiling joists, then through the sill to an access
junction box, and then down and underground to the pool panel attached
to the side of the pool house. Total distance is about 75'. It is in pvc
pipe the entire distance between the two electrical panels, and was
installed by an electrician and inspected and approved by the electrical
inspector.
All the GFCI breakers are in the pool's subpanel, not the main panel. I
also run the electricity for the pool house from this subpanel.

--
Bill
In Hamptonburgh, NY
To Email, remove the double zeroes after 'at'

Posted by Tom The Great on June 1, 2006, 2:35 pm
On 1 Jun 2006 03:13:40 -0700, Phillip77776666@yahoo.com wrote:

>I'm installing a 20A GFCI receptacle on my 4x4 deck post using the
>proper weather proof box and cover. I plan to run 12-2 UF wire from my
>garage subpanel (about 40ft.) to it, the GFCI outlet will have it's own
>20A breaker. BTW; The subpanel is on a 50A main breaker using 6/3 with
>ground cable; really doesn't have much on it, other than a 50 gallon
>water heater on a 30A double pole and also garage receptacles, five
>fluorescent strip lights, couple outside wall lights which are on a
>seperate 20A breaker.
>
>But, I'm confused; Do I need to run the wire through conduit? It's not
>going to be close to the ground or anywhere close to where it might get
>damaged. What about when I run the wire through the floor sill (inside
>a wall) of the garage to outside? Do I need to protect the wire? If so,
>could I just run the wire through ordinary short piece of 1/2" CPVC
>pipe? The GFCI outlet is for a pool pump motor, which draws about 13.5
>amps and will be running about 12 hours a day. I don't want to violate
>any NEC codes. Thanks for the help


I could just tell you what you already read in the NEC for underground
feeders, and pool equipment, but then it might not apply.

Your local codes could have more restrictive requirements. Check with
your local code enforcement.

Good luck,

Tom @ www.FreelancingProjects.com



Similar ThreadsPosted
Running wire to detached garage October 29, 2006, 1:28 am
Running wire to freestanding building October 30, 2006, 7:42 am
Running wire through block wall? November 9, 2008, 12:59 am
Having problems running wire up wall from basement May 20, 2006, 9:01 pm
Running Wire inside basement walls December 13, 2006, 4:24 pm
Running electrical wire below joist in boxed in ductwork??? August 26, 2007, 11:17 am
Running wire in finished ceiling on main floor August 21, 2008, 2:35 pm
el wire rope lighting electroluminescent FLEXIBLE NEON WIRE (KPT SERIES) September 5, 2006, 5:13 pm
el wire rope lighting electroluminescent FLEXIBLE NEON WIRE (KPT SERIES) September 5, 2006, 5:14 pm
Adding a GFCI outlet with two-wire (duplex) wire August 19, 2006, 12:18 pm