|
Posted by vijaynats@gmail.com on May 4, 2008, 4:25 pm
> A flaring tool with a 45 degree cone is required to create a flare
> on the end of the tube's.
>
> However as you obviously dont have ------------------------ONE
>
> Close =A0the =A0liquid =A0line valve and =A0pump down =A0the System, this
> transfers the refrigerant charge to the outside unit
> Close the Suction service valve and turn the unit OFF. =A0 =A0Leave
> the Flared ends of the tubing on the unit and with a Pipe Cutter
> cut the tube's 20 cm from the flare's. =A0 =A0 =A0Shorten the tubes and
> reconnect to the 20 cm pipe stubs with brazed unions.
> Loosen =A0the Suction =A0line Flare =A0nut, =A0then =A0crack =A0the =A0liq=
uid line
> valve. =A0 Allow the refrigerant to purge the air in the lines through
> the loose flare nut, Then tighten the nut.
> Open =A0both =A0the =A0Liquid line and Suction line service valves and
> turn the unit on.
> Take care to pump down fully and try not to lose to much of the
> refrigerant when purging air from the lines.
> The correct way of carrying out this work would be to close the
> liquid line service valve, bypass the low pressure switch and with
> the use of gauges pump down to a vacuum. =A0 =A0Close the Suction
> service =A0valve =A0and =A0then =A0break =A0the =A0vacuum =A0with =A0dry =
=A0Nitrogen.
> Shorten both the liquid and suction lines and leak test. =A0Evacuate
> the =A0lines =A0to 500 =A0microns =A0Hg =A0and break with dry Nitrogen the=
n
> Evacuate to 300 microns Hg. =A0 =A0Open both the liquid and suction
> service valves and adjust the unit charge.
>
>
>
>
>
> >I have a split AC system with the Outdoor unit just across the wall
> > where the indoor unit is fixed. The AC system comes with pipes that
> > are 3 meters long - whereas the actual length required is less than
> > 1.5 meters.
>
> > Right now the pipes are coiled together and tied to the outdoor unit.
> > When the AC is running, the pipes shake and vibrate a lot. I am
> > worried if it might affect the connections to the outdoor unit. Also
> > don't lengthy tubing reduce the efficiency of the AC?
>
> > Is is possible to cut and shorten the piping so that we don't have to
> > coil the same. I have seen many places where the pipes are short and
> > neatly clamped to the wall. I've read that the pipes need to be flared
> > at the end using some special tool after they are cut.
>
> > What is the best practice in such situations? Please let me know if
> > its ok =A0to shorten the pipes and clamp them to the wall after proper
> > insulation.
>
> > Thanks
>
> > Vijay- Hide quoted text -
>
> - Show quoted text -
Whoa thats some science to me! If you say shorten - then i'll call the
AC engineer and have him do it.
Thanks!
|