Posted by hcourtne on December 3, 2006, 11:43 am
I am currently renting an apartment with steam one pipe radiators.
When the heat is on in my bedroom, it causes the windows to fog to a
point where they are dripping, creating pools of water on the sills and
optimum conditions for mildew to grow.
Obviously steam is escaping, and I have realized that it is through the
air vent. I understand that the air vent should close when the steam
hits it, but clearly this is not, as on close inspection while it was
on I found there to be steam rapidly escaping from the vent. So my
question is, should the vent be cleaned, or should I contact my
building manager to get a replacement? Or is there another answer
entirely? My building manager isn't great at understanding a problem
when you talk to her (language barrier), so I would prefer to use
specific language that she can tell the maintenance man, rather than
broad, "it's not working", especially if it's something easy to fix.
Thanks in advance, I've seen you guys give some great advice.
|
|
Posted by Jimi on December 3, 2006, 12:06 pm
show/hide quoted text
>I am currently renting an apartment with steam one pipe radiators.
> When the heat is on in my bedroom, it causes the windows to fog to a
> point where they are dripping, creating pools of water on the sills and
> optimum conditions for mildew to grow.
> Obviously steam is escaping, and I have realized that it is through the
> air vent. I understand that the air vent should close when the steam
> hits it, but clearly this is not, as on close inspection while it was
> on I found there to be steam rapidly escaping from the vent. So my
> question is, should the vent be cleaned, or should I contact my
> building manager to get a replacement? Or is there another answer
> entirely? My building manager isn't great at understanding a problem
> when you talk to her (language barrier), so I would prefer to use
> specific language that she can tell the maintenance man, rather than
> broad, "it's not working", especially if it's something easy to fix.
> Thanks in advance, I've seen you guys give some great advice.
Yes, you could have a faulty PSV (Pressure Sensitive Valve). Close the
valves to the radiator and wait till the rad cools...Then replace the PSV.
These DO leak after years of service and is cause by scale build up,
weakening springs etc.. Make sure you replace the valve with the same
pressure rating... Jimi
show/hide quoted text
>
|
| Similar Threads | Posted | | Steam vent radiator threads stripped | April 2, 2007, 10:02 pm |
| steam radiator valve ? | October 23, 2005, 8:46 pm |
| Have old steam radiator, want to turn it off | December 17, 2005, 3:01 pm |
| steam radiator connecting nut | August 29, 2006, 2:50 pm |
| moving steam radiator | October 5, 2009, 12:39 pm |
| Steam radiator problem | January 10, 2010, 2:17 pm |
| Steam Radiator thread sealant? | October 15, 2005, 10:46 am |
| replacing steam radiator valves | February 20, 2006, 10:10 am |
| steam radiator leak at connection | October 24, 2006, 11:31 am |
| Steam radiator vents "sizzle" | December 6, 2006, 9:56 am |
|
|
|
> When the heat is on in my bedroom, it causes the windows to fog to a
> point where they are dripping, creating pools of water on the sills and
> optimum conditions for mildew to grow.
> Obviously steam is escaping, and I have realized that it is through the
> air vent. I understand that the air vent should close when the steam
> hits it, but clearly this is not, as on close inspection while it was
> on I found there to be steam rapidly escaping from the vent. So my
> question is, should the vent be cleaned, or should I contact my
> building manager to get a replacement? Or is there another answer
> entirely? My building manager isn't great at understanding a problem
> when you talk to her (language barrier), so I would prefer to use
> specific language that she can tell the maintenance man, rather than
> broad, "it's not working", especially if it's something easy to fix.
> Thanks in advance, I've seen you guys give some great advice.