Surge protector, roll your own

Home Repair - - If it ain't broken, don't fix it. Otherwise look here. 

Page 2 of 3       < 1 2 3 > last >> Bookmark this page:  YahooMyWeb Yahoo!  Google Google  Windows Live Favorites Windows Live  del.icio.us del.icio.us  digg digg  Add to Netscape Netscape
Subject Author Date
Surge protector, roll your own Rob Mills 07-11-2005
If you were  Registered and logged in, you could reply and use other advanced thread options
Posted by w_tom on July 12, 2005, 9:15 pm


Joules are a measure of energy. But that is all irrelevant
to MOVs. For MOVs, joules defines life expectancy. More
specifically, how fast the MOV will degrade. The manufacturer
defines MOV failure mode: degradation - not vaporization.
Joules is the parameter that defines that life expectancy.

Tony Hwang wrote:
> Hi,
> Joule is not a measurement of power it is unit of energy.
> Let me put it this way, if you get a direct hit nothing uch will
> work.
> Telling from real world experience.
> And real protector for whole house costs a lot. And surge current
> is much faster than breaker or fuse.
> Tony


Posted by CL (dnoyeB) Gilbert on July 13, 2005, 9:07 am

> After the last one had me going, I can't wait to see how this one
> transpires..
> Searcher
>
The last one In retrospect dumping the salt OUT OF the bags into wheel
barrow ( clean) spreading around the pool with shovel might of been a better
idea, to bad I didn't think of that.



Posted by Bob S. on July 12, 2005, 10:47 am




Rob Mills wrote:

> Been snooping around and notice that the cheap (office depot and etc)
> plastic strip (5 recep) surge protectors have only one MOV but the more
> expensive ones have one MOV at each receptacle. Looks to me as if you could
> use metal recep boxes that would hold two or three receps and place a MOV
> across each recep, put a metal cover on it and a short 3 wire 12 gauge cord
> and have a much better surge protector to protect sensitive equipment for
> not much more than the computer/office stores want for the plastic cased
> ones.

What's wrong with pulling the wall receptacle and placing a MOV across
the hot/ground terminals? Gets rid of the ugly box, protects anything
plugged into it plus down-stream receptacles. Of course you'd have to
remember where it was in case it ever shorted.

Bob S.



Posted by Rob Mills on July 12, 2005, 7:42 pm

Posted by w_tom on July 12, 2005, 9:08 pm

> After the last one had me going, I can't wait to see how this one
> transpires..
> Searcher
>
The last one In retrospect dumping the salt OUT OF the bags into wheel
barrow ( clean) spreading around the pool with shovel might of been a better
idea, to bad I didn't think of that.



Page 2 of 3       < 1 2 3 > last >>
Similar ThreadsPosted
Surge Protector April 24, 2006, 8:30 am
Whole house surge protector? July 6, 2005, 8:50 am
Whole House Surge Protector That Goes Right After The Meter ? August 4, 2005, 7:13 pm
Location For A Wired-In Surge Protector ? August 17, 2005, 8:00 am
Intermatic Whole House Surge Protector ? April 17, 2008, 11:38 am
Surge Protector for Friederich 24k btu Wall A/C Unit - Is it okay to use? November 8, 2007, 5:00 pm
For You Electrical Guys: Intermatic Surge Protector Quest., Please ? August 25, 2005, 11:13 am
Heater Hustlers from Canton again: HEAT SURGE Roll-n-Glow Fireplace December 12, 2007, 10:19 am
Painting: Cut Once Roll Twice September 18, 2005, 3:46 pm
Painting: Cut Once Roll Twice September 18, 2005, 3:50 pm

Contact Us | Privacy Policy

XML SitemapXML Sitemap