Posted by PSZach on July 14, 2006, 6:57 pm
Eric in North TX Wrote:
> I'm planing an install of a Takagi T-KD20 in the
first floor of a 2
> story addition. I'm a little confused by their install instructions.
> Do
> I need to go through the second story roof with the exhaust vent?
> My first choice would be to make it as short as possible. There are no
> first floor windows on that wall, & only 2 on the entire wall, both
> 15'
> or more from the intended location, there is a gable vent ~ 20' above
> the intended location.
The Takagi Exhaust Venting instructions place a lot of burden on the
installer
to be in accordance with the section on venting of equipment
in the latest
edition of the National Fuel Gas Code. Based on your
criteria, if the gable vent
has a negative pressure or in other words
does draft inwardly, then there should
be a concern.
For venting parts that would comply with Wall Thimble Termination
consider
visiting www.plumbersurplus.com .
For the actual 4” ProTech Systems FasNSeal Wall Thimble with
Termination
Telescoping Elbow Appliance Adapter mentioned in the Takagi
Exhaust Venting
instructions, click here….
http://www.plumbersurplus.com/ProductDetail.aspx?Prod=26849&Cat=306
Here some instructions from another manufacture “Rheem”
http://tinyurl.com/rcuhf
They talk about horizontal termination in the installation section.
--
PSZach
|

| |
Posted by MDT at Paragon Home Inspection on July 14, 2006, 9:32 pm
I have these installed in several buildings as sidewall vent units.
1) If your's is a freezing climate, make sure you install a TK-TV03
back draft preventer.
2) If you want output hotter than 122F, you will need to install an
external TK-RE02 controller.
3) You will need a TK-BK01 wall mount kit.
4) Takagi specs a TK-TV05 wall-mount terminator kit. It's a big unit,
make sure that you allow a full 16" stud bay for its installation, and
plan the heater location with this in mind. It's helpful to have the
fill kit on site so plumbers and electricians can visualize what's
involved.
5) Don't forget that the unit will need 120V power.
6) You will need 2x wall SS vent pipe and fittings (check with Takagi,
at the time I installed they had approved two manufactures), and HT
sealant. It's simplest if you order the pipe, fittings and TV-03 (if
used) from the same source, so everything fits.
7) You will need .75" gas pipe (or equivalent CSST) ALL THE WAY to the
heater - you are putting in a 190,000 BTU appliance - probably, larger
than your gas furnace or boiler - and you may need to upsize piping or
even, on low pressure NG systems, an unsized meter!
8) You will need a TPRV rated for 200K BTU.
On later installs I used these isolation valves, they make for a
cleaner install, you can order either .75" sweat or IPS:
http://www.plumbingstore.com/images/isolationvalves-50443.jpg
Michael Thomas
Paragon Home Inspection, LLC
Chicago, IL
mdtATparagoninspetsDOTcom
eight47-475-5668
|
|
Posted by Eric in North TX on July 15, 2006, 12:12 am
Thanks for your reply! That's a very detailed and helpful post.
I'll be using LPG and the proposed site is a couple of yards from the
tank, so a new line shouldn't be much problem, I'll talk to my propane
guy to see if I can flow enough gas to run it, and what to do if not,
he is a certified, licenced, LPG plumber, he will know what to do. I
may not need much chimney, as the unit should mount right to the
TK-TV05 wall-mount terminator kit. Everything is right there as it will
replace an electric one already occupying that site. It does freeze
here maybe 2 weeks a year, but the spot it will occupy will be somewhat
heated, it is a large utility closet under landing for the stairs.
though it won't be directly heated it should stay 50 degrees or better,
I'll still look into the back draft preventer.
|
Page 2 of 2 << first < 1 2
| Similar Threads | Posted | | Power Vent on Direct Vent Water Heater | January 8, 2006, 8:57 pm |
| direct vent vs. vent free gas fireplace | November 25, 2007, 8:41 am |
| Direct Vent Gas Dryer | May 27, 2008, 10:49 pm |
| direct vent water heater | November 29, 2006, 4:28 pm |
| Most efficient direct vent space heaters? | August 14, 2005, 3:51 pm |
| Power Direct Vent Water Heaters | November 16, 2005, 12:31 am |
| soffit vent - install from above or below ?? | September 1, 2006, 1:03 pm |
| dryer vent install | August 22, 2008, 8:23 am |
| Need advise on install of roof vent fan | May 23, 2007, 3:37 pm |
| How do I install a sump radon vent system | October 17, 2005, 6:00 pm |
|
|