|
Posted by RBM on May 31, 2006, 10:21 pm
Terminals RH and W are for heating and not used for air only. The four wire
system should work fine with that stat, but it sounds like doesn't have two
stage capability, so it's the wrong stat for the other unit
> Just bought a home with a bonus room upstairs - split unit AC.
> Thermostat on the first floor was a 2 stage totaline P474-0100 and
> upstairs was a single stage manual robertshaw CM200.
>
> I bought two Honeywell 5-2 Day Programmable Thermostat's to replace
> both. Replacing the bonus room went well. When I replaced the
> totaline the unit would not engage (nor the fan). All contacts were
> solid
>
> The bonus room was a four wire (no Rc, just Rh). The first floor had a
> five wire and the totaline marked it "C" - matching it up to Rc on the
> honeywell (I also removed the Rh/Rc jumper). Everything appeared to be
> wired up correctly.
>
> First - the Honeywell YRTH230B1009 stated - "For single stage heating
> and cooling or millivolt systems" - so from what I read I took a step
> back from the 2 stage totaline moving to the single stage honeywell.
>
> Second - was there a reason why there was a 4wire single stage in the
> bonus room vs the 5 wire 2 stage on the first floor - would it cause
> the problems when I installed the second honeywell?
>
> TIA.
>
|