|
Posted by DD_BobK on October 29, 2009, 9:51 pm
> > >> No, it takes too long to re-heat the boiler and all the water in the
> > >> pipes, radiators, and floor tubing. =A0It is always best to set it o=
nce
> > >> and leave it there all winter. =A0Too much energy is lost when all t=
hat
> > >> water is asked to re-heat all the surfaces again. =A0For example whe=
n I
> > >> feel the return manifold from the coils under my concrete slab after
> > >> the slab was allowed to cool, the return water is ice cold, all that
> > >> energy to reheat the slab. =A0No, bad asvice, best to keep it warm a=
nd
> > >> leave it there, saves tons of energy.
> > We use warm water here to shower. =A0I'd say that a higher % of people =
use
> > heat pumps or gas to heat rather than water. =A0In your case, MAYBE it =
is
> > cheaper to leave it on, but I think you are only quoting yourself, and =
no
> > analytic studies by any testing agency. =A0Can you find any said studie=
s? =A0I
> > don't doubt that you believe what you say is true, I just think that it=
is
> > not.
> > Steve
> Boiler installers never put daily "set back" thermostats on boilers,
> only forced air systems get those, and they tell you to set the
> thermostat once and leave it there.
> The rules are completely different for radiant heated buidings vs air
> heated buildings.
> In an air heated building you heat the air, in a radiant heated
> building you heat the building materials and that in turn heats the
> people. =A0When you lose all that stored energy it costs a fortune to
> recover it back in boiler usage. =A0There is nothing quite like the
> warmth of a radiant-heated house.
So the laws of themodynamics are different from system to system?
Heat its lost to the environment based on the difference in
temperature between the heated space & the unheated space. As the
temperature of the heated space falls, the heat loss also fails. When
the temperature of the heated space falls to that of the unheated
space, heat loss stops.
I believe you are confusing the "time" it takes to recover with "huge
amounts of energy are required to re-heat everything".
If you were correct in your thinking (& oyu are not) the whole concept
of temperature setback would not work (& it does).
cheers
Bob
|
> humidity in the boiler, rusting it out. And, boiler systems
> often do take a LONG time to recover temp.
>