Posted by Scott Townsend on February 25, 2007, 12:33 pm


Seems like I hear somewhere that putting some Vaseline on the o-ring of a
union was a good Idea. though I was not sure if that was for Water or
something else?

I will have several unions in my plumbing panel so I can replace parts and
pieces of it if a component fails. The unison are all PVC and are either 1
1/4" or 1 1/2". Should I add a bit of Vaseline to the o-ring?


For Automated Valves I was looking at the In-Line Sprinkler Valves. I have 2
Storage Tanks that I will be filling. Each of the Tanks will tell me if it
needs to be filled. With the Input I can decide which tank will get the
water and how long it will get it for. My question is, with the Sprinkler
Valves it seems like they need pressure on the input side to function
Correctly. If the Well is not pumping then there will be no Pressure on the
valve in-let. Will it close? If I leave the pump on and then turn the valve
off, then turn the pump off, how will that affect the pump with the back
pressure caused by the closed loop??

Thanks for any Suggestions and Input...

Scott<-



AppliancePartsPros.com, Inc.
Posted by Joe on February 25, 2007, 12:44 pm


On Feb 25, 11:33 am, "Scott Townsend" <scott-i@.-N0-
SPAMplease.enm.com> wrote:
> Seems like I hear somewhere that putting some Vaseline on the o-ring of a
> union was a good Idea. though I was not sure if that was for Water or
> something else?
>
> I will have several unions in my plumbing panel so I can replace parts and
> pieces of it if a component fails. The unison are all PVC and are either 1
> 1/4" or 1 1/2". Should I add a bit of Vaseline to the o-ring?
>
<snip>

Unles you are absolutely, positively, unconditionally sure that the O-
ring is compatible with Vaseline, don't do it. Rubber compounded for
water resistance just ain;t the same as rubber compounded for grease
and oil resistance. Since you don't know whether the O-ring is Buna-N,
silicone, Viton or whatever, just leave it alone. HTH

Joe



Similar ThreadsPosted
Washing Machine Water Inlet Valves - Cheap Source of Solonoid Control Valves? January 3, 2007, 7:11 pm
Copper unions - slip x mips? June 14, 2008, 10:18 pm
HELP HELP anyone out there? Unions leaking on new hot water heater June 17, 2008, 12:15 am
Automated Meter Reading (battery) ? November 4, 2007, 1:35 pm
Shower valves July 22, 2005, 7:25 pm
Leaking Valves November 26, 2005, 11:55 pm
thermstatic valves November 30, 2005, 10:46 am
Backflow Valves June 30, 2005, 4:47 pm
Air Admittance Valves in the U.S.? August 2, 2006, 5:43 pm
Valves on old radiators September 30, 2006, 7:08 pm

Contact Us | Privacy Policy

XML SitemapXML Sitemap