|
Posted by mm on June 21, 2007, 5:36 pm
On Thu, 21 Jun 2007 16:58:30 -0400, "RBM" <rbm2(remove
this)@optonline.net> wrote:
>keep in mind the OP says he has two double pole 40 amp breakers and two
>cables, one to the dryer and one to the A/C unit. Both cables show the same
>low voltage at the load ends.
I guess it's possible that the cables were one on top the another, and
the electrician drilled through both of them at the same time.
> He also says a continuity test shows all
>conductors are continuous
Maybe he made a mistake on that somehow. Maybe some alternate path he
didn't exclude.
A lof of maybes but something has to explain this strange problem.
>
>
>
>>> L1 to L2 around 80V
>>> L1 to N - 127V
>>> L2 to N - 11V
>>
>> Assuming the voltages were measured with an electronic VOM I'd say that L2
>> is open between the breaker panel and the load. Most likely your
>> electrician cut or drilled through it.
>>
>> Note that a 220/240V load doesn't care about the neutral; it only cares
>> about L1-L2.
>>
>>
>>
>
|