Home Page link

Voltage drop

Home Repair - - If it ain't broken, don't fix it. Otherwise look here. 

Bookmark this page:  YahooMyWeb Yahoo!  Google Google  Windows Live Favorites Windows Live  del.icio.us del.icio.us  digg digg  Add to Netscape Netscape
Subject Author Date
Voltage drop Terry 07-10-2007
|   `--> Re: Voltage drop William Underhi...07-11-2007
If you were  Registered and logged in, you could reply and use other advanced thread options
Posted by Terry on July 10, 2007, 6:29 pm
I have heard in the trade as a general rule if you are using #12 wire
for a 20A circuit you should go to #10 if the run is over 100 ft.
The fan #14 or #12 thread prompted me to just do a quick check at one
of the voltage drop web pages.
http://www.csgnetwork.com/voltagedropcalc.html
If you use this web page and try using 16A which would be the max on a
20A circuit you get 5% voltage drop in just the branch circuit.
Posted by Doug Miller on July 10, 2007, 8:25 pm
show/hide quoted text
The maximum load on a 20A circuit is... any guesses? ...wait for it... 20A.
16A is the maximum *continuous* load on a 20A circuit.
--
Regards,
Doug Miller (alphageek at milmac dot com)
It's time to throw all their damned tea in the harbor again.
Posted by nosmo_king58 on July 11, 2007, 3:35 pm
On Jul 10, 8:25 pm, spamb...@milmac.com (Doug Miller) wrote:
show/hide quoted text
Just to be anal, the maximum load on a 20A circuit can be far greater
than 20 amps, at least for a short period of time. According to the
Trip Curves on the Square D web site, their QO series of breakers can
handle a 2x load (or in this case, 40 amps) for just under 10 seconds
before tripping.
Posted by William Underhill on July 11, 2007, 4:44 pm
nosmo_king58@yahoo.com wrote:
show/hide quoted text
Hm. Now you've got me curious; have to go to Federal Pioneer and get the
Stab-Lok series data sheets. Wonder what the instantaneous trip rating is?
Yours aye,
W. Underhill
--
"Take sides! Always take sides! You may sometimes be wrong - but the man
who refuses to take sides must *always* be wrong! Heaven save us from
poltroons who fear to make a choice!" R.A. Heinlein, "Double Star"
Posted by M Q on July 11, 2007, 2:51 pm
Terry wrote:
show/hide quoted text
My copy of NEC (1990 -- somewhat obsolete) only mentions voltage drop
in FPN's (non-manditory notes). It recomends a max of 3% on branch
circuits "at the farthest outlet of power, heating, or lighting loads",
and a max of 5% on both feeder and branch circuit.
10ga copper is about 1.25 ohms / 1000', and
12ga copper is about 2 ohms / 1000', and
14ga copper is about 3.1 ohms / 1000'
3% of 120v is 3.6v.
100' of 12ga is actually 200' (hot & neutral) is .4 ohms
so 3.6/.4 = 9 amps for 3% voltage drop at 100'.
10 ga. will give you 14.4 amps at 100' and
14 ga. will give you 5.8 amps at 100'.
Of course you may be willing to withstand greater voltage drops.
(and yes, you get 5.33% voltage drop at 16A on 100' of #12: .4*16/120)
Similar ThreadsPosted
Will my voltage drop? September 5, 2006, 3:25 pm
Voltage drop in circuit to Dishwasher December 18, 2006, 3:20 pm
Cold weather cause voltage drop? January 25, 2007, 11:01 pm
Voltage drop - panel or utility issue? March 26, 2006, 3:04 pm
Combining wires to avoid voltage drop? 12/4 cable? October 26, 2005, 10:38 am
Calculating voltage drop, wire gauge ampacity over distance August 26, 2007, 6:40 pm
MR16 - low voltage or line voltage January 10, 2006, 9:04 pm
New Power Drop August 27, 2007, 12:49 am
OT: Drop in value of homes February 23, 2008, 4:10 pm
Drop down stairs August 19, 2008, 2:31 pm

Contact Us | Privacy Policy

XML SitemapXML Sitemap