Home Page link

Water pipe size

Home Repair - - If it ain't broken, don't fix it. Otherwise look here. 

Page 2 of 3       < 1 2 3 > last >> Bookmark this page:  YahooMyWeb Yahoo!  Google Google  Windows Live Favorites Windows Live  del.icio.us del.icio.us  digg digg  Add to Netscape Netscape
Subject Author Date
Water pipe size PipeDown 08-02-2005
`--> Re: Water pipe size Lawrence Wasser...08-03-2005
If you were  Registered and logged in, you could reply and use other advanced thread options
Posted by PipeDown on August 2, 2005, 11:36 pm



>> > Going from small to big won't cause much of a problem, aside from a "if
>> > you draw too much from one faucet, you might suck air in another"
>> > factor.
>
>> You would never suck air into a fixture unless for some very unusual
>> reason
>> you were pumping warter out of another fixture at a rate greater than the
>> source can replenish it. Excessive flow at one fixture would cause a
>> reduced flow at all other fixtures on the branch since all are passively
>> powered by available water pressure. Only if a fixture were actively
>> accelerating the water would a negative pressure develop in the pipe to
>> cause air sucking.
>
> Heh, no, sorry.
>
> Take a two story house with heavily restricted water feed. Turn on a
> faucet
> upstairs. Now, go turn on another faucet on downstairs.
>
> Do you hear the faucet upstairs sucking air?
>
> We do ;-)
> --
> Chris Lewis, Una confibula non set est
> It's not just anyone who gets a Starship Cruiser class named after them.


Briefly said, gravity would be that additional accelerating factor.

Perhaps I was being narrow sighted since I am in a single story house but
for that to happen the weight of the water column in vertical pipe leading
upstairs would need to exceed the static water pressure minus that pressure
relieved by the open downstairs fixture. In which case the 1/2" pipe would
be advised due to the reduced weight of the water column. Such a situation
should only occur in an installation flawed by inadequate water pressure or
too large pipes for a given pressure/flow. I can also see that a reducing
fitting an just the wrong spot on a vertical pipe could have unexpected
consequences by changing the static water pressure at that point (a problem
which should not happen in a horizontal run because there is no pressure
gradient under static conditions)

Your reply may have been essentially correct but it sure was confusing. I'm
not arguing, just trying to understand completely. In fact I am still
looking for a way to calculate the head pressure for each of the two cases
of 10' vertical pipe 1/2" and 3/4" . While it is obvious that water in a
3/4" pipe weighs more, the difference in area (of the pipe diameter) would
yeild different PSI measurements which might be closer (i.e. mass is
distributed over a larger area in the 3/4" pipe). Maybe I'll post later if
I can puzzle it out to my satisfaction, dosen't seem hard just short on time
and willpower now.








Tankless Water Heaters 468x60
Posted by Harry K on August 2, 2005, 5:48 pm



PipeDown wrote:
> >> > Going from small to big won't cause much of a problem, aside from a "if
> >> > you draw too much from one faucet, you might suck air in another"
> >> > factor.
> >
> >> You would never suck air into a fixture unless for some very unusual
> >> reason
> >> you were pumping warter out of another fixture at a rate greater than the
> >> source can replenish it. Excessive flow at one fixture would cause a
> >> reduced flow at all other fixtures on the branch since all are passively
> >> powered by available water pressure. Only if a fixture were actively
> >> accelerating the water would a negative pressure develop in the pipe to
> >> cause air sucking.
> >
> > Heh, no, sorry.
> >
> > Take a two story house with heavily restricted water feed. Turn on a
> > faucet
> > upstairs. Now, go turn on another faucet on downstairs.
> >
> > Do you hear the faucet upstairs sucking air?
> >
> > We do ;-)
> > --
> > Chris Lewis, Una confibula non set est
> > It's not just anyone who gets a Starship Cruiser class named after them.
>
>
> Briefly said, gravity would be that additional accelerating factor.
>
> Perhaps I was being narrow sighted since I am in a single story house but
> for that to happen the weight of the water column in vertical pipe leading
> upstairs would need to exceed the static water pressure minus that pressure
> relieved by the open downstairs fixture. In which case the 1/2" pipe would
> be advised due to the reduced weight of the water column. Such a situation
> should only occur in an installation flawed by inadequate water pressure or
> too large pipes for a given pressure/flow. I can also see that a reducing
> fitting an just the wrong spot on a vertical pipe could have unexpected
> consequences by changing the static water pressure at that point (a problem
> which should not happen in a horizontal run because there is no pressure
> gradient under static conditions)
>
> Your reply may have been essentially correct but it sure was confusing. I'm
> not arguing, just trying to understand completely. In fact I am still
> looking for a way to calculate the head pressure for each of the two cases
> of 10' vertical pipe 1/2" and 3/4" . While it is obvious that water in a
> 3/4" pipe weighs more, the difference in area (of the pipe diameter) would
> yeild different PSI measurements which might be closer (i.e. mass is
> distributed over a larger area in the 3/4" pipe). Maybe I'll post later if
> I can puzzle it out to my satisfaction, dosen't seem hard just short on time
> and willpower now.

No, a column of water 10 ft high will produce about 4.3 psi whether
that column is 1/2" or 5'. Seems counter intuitive but them is the
facts as I was taught in my last physics class ummmmm years ago ;).
Total weight of water depends on column size but the pressure per sq
inch doesn't change.

Harry K



Posted by PipeDown on August 3, 2005, 12:52 am



>
> PipeDown wrote:
>> >> > Going from small to big won't cause much of a problem, aside from a
>> >> > "if
>> >> > you draw too much from one faucet, you might suck air in another"
>> >> > factor.
>> >
>> >> You would never suck air into a fixture unless for some very unusual
>> >> reason
>> >> you were pumping warter out of another fixture at a rate greater than
>> >> the
>> >> source can replenish it. Excessive flow at one fixture would cause a
>> >> reduced flow at all other fixtures on the branch since all are
>> >> passively
>> >> powered by available water pressure. Only if a fixture were actively
>> >> accelerating the water would a negative pressure develop in the pipe
>> >> to
>> >> cause air sucking.
>> >
>> > Heh, no, sorry.
>> >
>> > Take a two story house with heavily restricted water feed. Turn on a
>> > faucet
>> > upstairs. Now, go turn on another faucet on downstairs.
>> >
>> > Do you hear the faucet upstairs sucking air?
>> >
>> > We do ;-)
>> > --
>> > Chris Lewis, Una confibula non set est
>> > It's not just anyone who gets a Starship Cruiser class named after
>> > them.
>>
>>
>> Briefly said, gravity would be that additional accelerating factor.
>>
>> Perhaps I was being narrow sighted since I am in a single story house but
>> for that to happen the weight of the water column in vertical pipe
>> leading
>> upstairs would need to exceed the static water pressure minus that
>> pressure
>> relieved by the open downstairs fixture. In which case the 1/2" pipe
>> would
>> be advised due to the reduced weight of the water column. Such a
>> situation
>> should only occur in an installation flawed by inadequate water pressure
>> or
>> too large pipes for a given pressure/flow. I can also see that a
>> reducing
>> fitting an just the wrong spot on a vertical pipe could have unexpected
>> consequences by changing the static water pressure at that point (a
>> problem
>> which should not happen in a horizontal run because there is no pressure
>> gradient under static conditions)
>>
>> Your reply may have been essentially correct but it sure was confusing.
>> I'm
>> not arguing, just trying to understand completely. In fact I am still
>> looking for a way to calculate the head pressure for each of the two
>> cases
>> of 10' vertical pipe 1/2" and 3/4" . While it is obvious that water in a
>> 3/4" pipe weighs more, the difference in area (of the pipe diameter)
>> would
>> yeild different PSI measurements which might be closer (i.e. mass is
>> distributed over a larger area in the 3/4" pipe). Maybe I'll post later
>> if
>> I can puzzle it out to my satisfaction, dosen't seem hard just short on
>> time
>> and willpower now.
>
> No, a column of water 10 ft high will produce about 4.3 psi whether
> that column is 1/2" or 5'. Seems counter intuitive but them is the
> facts as I was taught in my last physics class ummmmm years ago ;).
> Total weight of water depends on column size but the pressure per sq
> inch doesn't change.
>
> Harry K
>

Thats what I thought but a reducing union at the bottom would increase the
PSI by reducing the area while keeping the water column the same weight. A
reducing Tee would be OK as long as the size does not change in the vertical
direction




Posted by Don Young on August 2, 2005, 10:31 pm


No, you can't increase the pressure of a water column by reducing the pipe
size anywhere in any direction. A 10 foot high cone with point at the bottom
develops exactly the same pressure at the bottom as a 10 foot high cylinder.
Also water pressure is exactly the same in a sideways direction as downward
at any given point. Any increase in force (pounds) can only occur with a
corresponding increase in area (square inches) so the pressure (pounds per
square inch) is constant. I am not sure but I think that is known as
"Pascal's Law".
Don Young

>
>>
>> PipeDown wrote:
>>> >> > Going from small to big won't cause much of a problem, aside from a
>>> >> > "if
>>> >> > you draw too much from one faucet, you might suck air in another"
>>> >> > factor.
>>> >
>>> >> You would never suck air into a fixture unless for some very unusual
>>> >> reason
>>> >> you were pumping warter out of another fixture at a rate greater than
>>> >> the
>>> >> source can replenish it. Excessive flow at one fixture would cause a
>>> >> reduced flow at all other fixtures on the branch since all are
>>> >> passively
>>> >> powered by available water pressure. Only if a fixture were actively
>>> >> accelerating the water would a negative pressure develop in the pipe
>>> >> to
>>> >> cause air sucking.
>>> >
>>> > Heh, no, sorry.
>>> >
>>> > Take a two story house with heavily restricted water feed. Turn on a
>>> > faucet
>>> > upstairs. Now, go turn on another faucet on downstairs.
>>> >
>>> > Do you hear the faucet upstairs sucking air?
>>> >
>>> > We do ;-)
>>> > --
>>> > Chris Lewis, Una confibula non set est
>>> > It's not just anyone who gets a Starship Cruiser class named after
>>> > them.
>>>
>>>
>>> Briefly said, gravity would be that additional accelerating factor.
>>>
>>> Perhaps I was being narrow sighted since I am in a single story house
>>> but
>>> for that to happen the weight of the water column in vertical pipe
>>> leading
>>> upstairs would need to exceed the static water pressure minus that
>>> pressure
>>> relieved by the open downstairs fixture. In which case the 1/2" pipe
>>> would
>>> be advised due to the reduced weight of the water column. Such a
>>> situation
>>> should only occur in an installation flawed by inadequate water pressure
>>> or
>>> too large pipes for a given pressure/flow. I can also see that a
>>> reducing
>>> fitting an just the wrong spot on a vertical pipe could have unexpected
>>> consequences by changing the static water pressure at that point (a
>>> problem
>>> which should not happen in a horizontal run because there is no pressure
>>> gradient under static conditions)
>>>
>>> Your reply may have been essentially correct but it sure was confusing.
>>> I'm
>>> not arguing, just trying to understand completely. In fact I am still
>>> looking for a way to calculate the head pressure for each of the two
>>> cases
>>> of 10' vertical pipe 1/2" and 3/4" . While it is obvious that water in
>>> a
>>> 3/4" pipe weighs more, the difference in area (of the pipe diameter)
>>> would
>>> yeild different PSI measurements which might be closer (i.e. mass is
>>> distributed over a larger area in the 3/4" pipe). Maybe I'll post later
>>> if
>>> I can puzzle it out to my satisfaction, dosen't seem hard just short on
>>> time
>>> and willpower now.
>>
>> No, a column of water 10 ft high will produce about 4.3 psi whether
>> that column is 1/2" or 5'. Seems counter intuitive but them is the
>> facts as I was taught in my last physics class ummmmm years ago ;).
>> Total weight of water depends on column size but the pressure per sq
>> inch doesn't change.
>>
>> Harry K
>>
>
> Thats what I thought but a reducing union at the bottom would increase the
> PSI by reducing the area while keeping the water column the same weight. A
> reducing Tee would be OK as long as the size does not change in the
> vertical direction
>




Posted by Harry K on August 3, 2005, 6:36 am



Don Young wrote:
> No, you can't increase the pressure of a water column by reducing the pipe
> size anywhere in any direction. A 10 foot high cone with point at the bottom
> develops exactly the same pressure at the bottom as a 10 foot high cylinder.
> Also water pressure is exactly the same in a sideways direction as downward
> at any given point. Any increase in force (pounds) can only occur with a
> corresponding increase in area (square inches) so the pressure (pounds per
> square inch) is constant. I am not sure but I think that is known as
> "Pascal's Law".
> Don Young
>

<snip>

Right. The reducing tee merely changes the size of the column to that
of the output of the tee.

Harry K



Page 2 of 3       < 1 2 3 > last >>
Similar ThreadsPosted
What size hot water pipe should I use? April 3, 2008, 7:35 am
Re: Plumbing: What size hot water pipe do I need? April 3, 2008, 9:14 am
Re: Plumbing: What size hot water pipe do I need? April 3, 2008, 9:50 am
Sorry about the double post Re: Hot water pipe size April 3, 2008, 7:39 am
flue pipe size for venting water heater August 27, 2007, 6:02 pm
gas pipe size October 30, 2008, 6:16 pm
Size of pipe to the Septic Tank? August 25, 2006, 1:20 am
Plumbing - Pipe size question May 22, 2007, 2:54 pm
size of pipe to shower riser? July 28, 2008, 10:24 pm
Re: size of pipe to shower riser? July 29, 2008, 12:15 pm

Contact Us | Privacy Policy

XML SitemapXML Sitemap