What kind of circuitry does this device need?

Home Repair - - If it ain't broken, don't fix it. Otherwise look here. 

Page 1 of 3       1 2 3 > last >> Bookmark this page:  YahooMyWeb Yahoo!  Google Google  Windows Live Favorites Windows Live  del.icio.us del.icio.us  digg digg  Add to Netscape Netscape
Subject Author Date
What kind of circuitry does this device need? Aaron Fude 05-23-2008
If you were  Registered and logged in, you could reply and use other advanced thread options
Posted by Aaron Fude on May 23, 2008, 5:16 am
Hi,

I'm installing the panasonic FV-11VHL1.

(http://www2.panasonic.com/consumer-electronics/shop/Building-Products/
Ventilation-Systems/Ceiling-Insert-Fans/model.FV-11VHL1)

I have concluded that this device will need its own circuit, but would
a 15amp suffice? And if yes, is it OK to go with 14 gauge?

Many thanks in advance!

Aaron Fude

Posted by ransley on May 23, 2008, 9:58 am
> Hi,
>
> I'm installing the panasonic FV-11VHL1.
>
> (http://www2.panasonic.com/consumer-electronics/shop/Building-Products/
> Ventilation-Systems/Ceiling-Insert-Fans/model.FV-11VHL1)
>
> I have concluded that this device will need its own circuit, but would
> a 15amp suffice? And if yes, is it OK to go with 14 gauge?
>
> Many thanks in advance!
>
> Aaron Fude

The link did not work, but if its a bath fan they dont use much maybe
150 watt for the blower

Posted by bud-- on May 23, 2008, 11:44 am
ransley wrote:
>> Hi,
>>
>> I'm installing the panasonic FV-11VHL1.
>>
>> (http://www2.panasonic.com/consumer-electronics/shop/Building-Products/
>> Ventilation-Systems/Ceiling-Insert-Fans/model.FV-11VHL1)
>>
>> I have concluded that this device will need its own circuit, but would
>> a 15amp suffice? And if yes, is it OK to go with 14 gauge?
>>
>> Many thanks in advance!
>>
>> Aaron Fude
>
> The link did not work, but if its a bath fan they dont use much maybe
> 150 watt for the blower

It includes a 1400W heater and runs at 12A max. The US code wants a
separate 15A #14 circuit (min).

--
bud--

Posted by Aaron Fude on May 23, 2008, 12:19 pm
Thanks!. Then what I am is this: is it OK to bringe a 12 gauge wire
from the panel to the switchbox, but then have 14 gauge wires go from
the switch box to the unit. Otherwise, I would need *five* 12-gauge
wires in the switchbox, which just won't fit!

Thanks!

Aaron


Posted by David Nebenzahl on May 24, 2008, 1:18 am
On 5/23/2008 9:19 AM Aaron Fude spake thus:

> Thanks!. Then what I am is this: is it OK to bringe a 12 gauge wire
> from the panel to the switchbox, but then have 14 gauge wires go from
> the switch box to the unit. Otherwise, I would need *five* 12-gauge
> wires in the switchbox, which just won't fit!

Since the circuit is rated at 15 amps, which #14 is capable of safely
carrying, then yes. But why do it that way? Have you already run #12 to
the box?


--
The best argument against democracy is a five-minute
conversation with the average voter.

- Attributed to Winston Churchill

Page 1 of 3       1 2 3 > last >>
Similar ThreadsPosted
GFCI device December 7, 2005, 12:13 pm
Electronic device April 16, 2006, 6:13 pm
30a plug on a 10a device? December 22, 2006, 11:06 am
RedyTemp device February 15, 2007, 7:12 am
Measuring device suggestions March 15, 2007, 10:29 pm
Septic monitoring device September 7, 2007, 10:12 am
Siphon Device Needed October 14, 2007, 6:45 am
hot water recirculating device November 29, 2007, 12:10 am
Adding a combination device January 27, 2008, 5:46 pm
What is a water well ejector device? April 23, 2006, 10:59 am

Contact Us | Privacy Policy

XML SitemapXML Sitemap