|
Posted by Speedy Jim on July 26, 2007, 4:15 pm
M Q wrote:
> over40pirate@aol.com wrote:
>
>> I am trying to find out the wire sizes needed for a 250' underground
>> feeder from the main panel, to a sub panel in the garage. I would like
>> a 220, 50 or 60 amp service.
>> What type wire would be the least expensive/
>
>
> There are two issues here for wire size:
> 1) Minimum code required size for the current, regardless of length.
> That would be 8AWG for copper and 6AWG for Aluminum, for either 50 or
> 60A.
>
> 2) Acceptable voltage drop at maximum current for that length:
> My old 1990 NEC does not specify, but only recommends a voltage drop
> percentage of 3% for the feeder or 5% including the branch circuit.
> This would be based on the actual load, not the subpanel rating.
> Also, if you will always have a balanced load, you can compute it
> based on percentage of 240 V, and you may be able to get away with
> a lesser wire for the neutral, if you may have a way unbalanced load,
> you would have to compute it based on a percentage of 120 V.
> Here is a bit of data:
>
> AWG ohms/500' V drop @ 50A % of 240V
> 6 Cu .25 12.5 5.2
> 4 Cu .154 7.7 3.2
> 2 Cu .1 5.0 2.1
>
> 6 Al .404 20.2 8.4
> 4 Al .254 12.7 5.3
> 2 Al .16 8.0 3.3
> 1 Al .13 6.3 2.6%
>
> You may find Aluminum to be cheaper for those wire sizes
> even though you need a larger size for Al.
>
> If you need to ask these questions, you probably should be talking
> to you local building inspector because there are many other
> code issues to do this right.
>
Possible typo: #8 Cu won't do it for a 60 Amp feeder.
|