>>wanting to feed a branch box with a 60a breaker (#6 copper) thru EMT.
>>
>>This may be a stupid question, but is there anything in the NEC to
>>prohibit
>>using double #10's to get the amperage?
>
> Yes, there is. Section 310-4 explicitly *permits* parallelling conductors
> of
> size 1/0 or *larger*, and thus by implication prohibits it for smaller
> conductors.
>
> --
> Regards,
> Doug Miller (alphageek at milmac dot com)
>