Home Page link

breaker AIR rating

Home Repair - - If it ain't broken, don't fix it. Otherwise look here. 

Bookmark this page:  YahooMyWeb Yahoo!  Google Google  Windows Live Favorites Windows Live  del.icio.us del.icio.us  digg digg  Add to Netscape Netscape
Subject Author Date
breaker AIR rating zeb7k 03-17-2007
If you were  Registered and logged in, you could reply and use other advanced thread options
Posted by on March 17, 2007, 11:10 pm


I understand that AIR stands for Ampere Interrupting Rating.

I'm wiring a 200A service for a residence with a Q0 load center.
Where in the NEC (pun) does it show what AIR rating I should use when
selecting breakers? When should I use 10,000 AIR, when should I use
22,000 AIR or higher?

--zeb


PexSupply QuikTrak 468x60
Posted by Bud-- on March 18, 2007, 2:41 am


zeb7k@hotmail.com wrote:
> I understand that AIR stands for Ampere Interrupting Rating.
>
> I'm wiring a 200A service for a residence with a Q0 load center.
> Where in the NEC (pun) does it show what AIR rating I should use when
> selecting breakers? When should I use 10,000 AIR, when should I use
> 22,000 AIR or higher?
>

NEC 110.9 requires the overcurrent devices to have an interruput rating
high enough to interruupt the available fault current. Get the available
fault current from the utility. It depends on supply wire size and
length, transformer % impedance, fault current available to the supply
transformer. For a large installation with multiple panels, the
available fault current at panels is calculated by the designer,
commonly an engineer. The designer also needs to know the fault current
avilable from the utility. I would guess 10,000 would be high enough.

--
bud--


Similar ThreadsPosted
R-rating of Bow Window August 1, 2007, 3:44 pm
Rating contractors September 3, 2007, 9:46 pm
PVC Conduit Fill Rating? June 19, 2006, 4:28 pm
Contractor rating site August 30, 2006, 6:11 pm
plywood deflection rating April 18, 2008, 10:27 am
Help picking Seer rating for A/C unit March 7, 2006, 9:59 am
What does BTUH rating mean on water heaters? July 11, 2006, 1:47 pm
Benjamin Moore paint low rating March 29, 2008, 3:19 pm
seer rating doesn't match power draw July 29, 2005, 7:31 pm
What is the gauge rating of the four wires for a four pin oven pigtail February 9, 2007, 12:14 pm

Contact Us | Privacy Policy

XML SitemapXML Sitemap