Posted by martind on August 10, 2007, 7:38 pm
I replaced a sink garbage disposal. When turned on it runs fine but as soon
as I shut off the switch the breaker trips. I replaced the wall switch, but
still have the same problem. Any suggestions?
Marty


Posted by RBM on August 10, 2007, 7:55 pm
If it's wired through an AFCI or GFCI, the unit may have a ground fault. Try
a standard breaker


>I replaced a sink garbage disposal. When turned on it runs fine but as
>soon as I shut off the switch the breaker trips. I replaced the wall
>switch, but still have the same problem. Any suggestions?
> Marty



Similar ThreadsPosted
New GE disposal - loud click when turned on? December 26, 2005, 3:50 pm
Slight shock after the power is turned off to circuit November 8, 2005, 9:39 am
Furnace Comes On When Circuit Breaker Turned On To Central Unit September 3, 2006, 9:20 pm
Re: air conditioner circuit breaker trips April 16, 2006, 6:40 am
Re: air conditioner circuit breaker trips April 16, 2006, 8:18 am
Re: Circuit breaker for kitchen trips March 30, 2007, 8:56 am
Re: air conditioner circuit breaker trips April 17, 2006, 8:49 am
Re: air conditioner circuit breaker trips May 31, 2006, 10:21 am
Re: Circuit breaker for kitchen trips March 30, 2007, 1:35 pm
Re: Circuit breaker for kitchen trips March 30, 2007, 1:26 pm

Contact Us | Privacy Policy

XML SitemapXML Sitemap