|
Posted by Tom Horne, Electrician on July 15, 2007, 1:29 pm
timO' wrote:
> I'm getting ready to hang a 200A load center and also connect up a
> 100A disconnect.
>
> At thge load center location the two branch circuits are coming out of
> the side of the structure which has vinyl siding over wood. one of the
> branch circuits is currently connected to the old 100A meter.
> on the bottom back of the new load center there are two knockout s for
> wires one on each corner.
> my two branch circuits are SER4/4/4/2 cable one above the other about
> two inches apart, and I'd like to feed them into the load center
> through the back so there is no exposed wire.
> So the question is what are some approved ways of doing this?
>
> can i knock out the knock out then drill another hole adjacent to it
> so i have a figure 8 opening? or make one big round hole? the wires
> are about .75" diameter. the spacing is about 2.625 center to center,
> and the overall hole diameter would need to be a clear 3.5" Don't they
> need to be clamped? (they're already weather sealed.
> I want the panel to sit tight up to the mounting surface. the other
> question is the SER into the disconnect. for the sake of neatness and
> safety I want to lay the incoming and outgoing wires flat against the
> side of the box, but the onlt connectors my supply house has are
> straight ones. FOr lighter gauge romex there are 90 degree connectors,
> but my guy says he is unaware of such a connector for this size wire.
>
The terms you are using are causing me some confusion. Is the item you
are calling a load center the meter enclosure? If yes then you cannot
cut additional holes in it. Some utilities will not allow the service
conductors to be run through the back of a meter enclosure. If what you
are referring to is a Combination meter enclosure and service
disconnecting means then that may not apply to it. Provide the make and
the model number of the device you are talking about and I can be of
more help.
--
Tom Horne
"This alternating current stuff is just a fad. It is much too dangerous
for general use." Thomas Alva Edison
|