Posted by karla on February 10, 2005, 6:19 pm


I pounded in a copper 8 ft ground rod and purchased a clamp.Queston #1 What
size solid copper wire do I need to buy?(4 or 6)
#2 Does the wire attach to the meter box or the sevice panel.(or both)? 200
amp ,new construction disconnect and main inside service panel. The service
panel and meter box are connected with grey pvc not emt.
thanks Gary





PexSupply Save 10 468x60
Posted by xrongor on February 10, 2005, 4:22 pm


i believe code specifies 2 rods.

randy

>I pounded in a copper 8 ft ground rod and purchased a clamp.Queston #1 What
>size solid copper wire do I need to buy?(4 or 6)
> #2 Does the wire attach to the meter box or the sevice panel.(or both)?
> 200 amp ,new construction disconnect and main inside service panel. The
> service panel and meter box are connected with grey pvc not emt.
> thanks Gary
>
>




Posted by RBM on February 10, 2005, 8:02 pm


Two rods, # 4 for 200 amp attached at main disconnect, check with your
utility company about a jumper to meter pan, usually the neutral grounds the
pan
>i believe code specifies 2 rods.
>
> randy
>
>>I pounded in a copper 8 ft ground rod and purchased a clamp.Queston #1
>>What size solid copper wire do I need to buy?(4 or 6)
>> #2 Does the wire attach to the meter box or the sevice panel.(or both)?
>> 200 amp ,new construction disconnect and main inside service panel. The
>> service panel and meter box are connected with grey pvc not emt.
>> thanks Gary
>>
>>
>
>




Posted by on February 12, 2005, 2:56 am


On Thu, 10 Feb 2005 13:22:05 -0700, "xrongor"

>i believe code specifies 2 rods.
>

If memory serves me right, only if you can't get a 25 ohm or less
resistance to ground. Then you put the second one in for good
measure.



>randy
>
>>I pounded in a copper 8 ft ground rod and purchased a clamp.Queston #1 What
>>size solid copper wire do I need to buy?(4 or 6)
>> #2 Does the wire attach to the meter box or the sevice panel.(or both)?
>> 200 amp ,new construction disconnect and main inside service panel. The
>> service panel and meter box are connected with grey pvc not emt.
>> thanks Gary
>>
>>
>


later,

tom @ www.medicaljoblist.com




Posted by zxcvbob on February 10, 2005, 8:36 pm


karla wrote:
> I pounded in a copper 8 ft ground rod and purchased a clamp.Queston #1 What
> size solid copper wire do I need to buy?(4 or 6)

Either is adequate, but there's not much difference in cost and the #4
requires no physical protection whereas the #6 might.

> #2 Does the wire attach to the meter box or the sevice panel.(or both)? 200
> amp ,new construction disconnect and main inside service panel. The service
> panel and meter box are connected with grey pvc not emt.
> thanks Gary
>

It attaches to whichever box contains the main disconnect for the
building. (Or is it the main overcurrent protection device? Usually
they are the same thing.)

Also, you should use 2 ground rods; it's cheaper and easier than testing
the impedence to make sure it is less than 25 ohms. A third ground rod
is not required even if the GEC impedence is still more than 25 ohms
after you add the 2nd electrode.

Don't forget to ground your water pipe within 6 feet of where it enters
the building, and put a #6 jumper wire around the water meter so the
circuit is not broken if the meter is removed.

Best regards,
Bob


Page 1 of 2       1 2 > last >>
Similar ThreadsPosted
Breaker box main ground help September 28, 2006, 1:18 am
GFI Neutral and distance to the main ground December 5, 2005, 10:52 am
Replacing main ground rods November 27, 2006, 7:46 pm
Ground current through water main/meter October 30, 2006, 11:20 am
200 amp main cabinet with 100 amp main breaker? March 24, 2006, 6:46 pm
Clog in main sewer line or drain lines running to main line. May 30, 2007, 4:10 pm
Main panel to main panel wiring in converting multi-family to single family dwelling November 9, 2006, 6:35 pm
Bonded ground wires vs. earth ground wire December 25, 2006, 6:08 pm
New Main Panel Help April 11, 2008, 2:04 pm
Main Panel July 10, 2008, 11:30 pm

Contact Us | Privacy Policy

XML SitemapXML Sitemap