need help/suggestions with two story heating/cooling

Home Repair - - If it ain't broken, don't fix it. Otherwise look here. 

Bookmark this page:  YahooMyWeb Yahoo!  Google Google  Windows Live Favorites Windows Live  del.icio.us del.icio.us  digg digg  Add to Netscape Netscape
Subject Author Date
need help/suggestions with two story heating/cooling andrew 09-11-2006
If you were  Registered and logged in, you could reply and use other advanced thread options
Posted by andrew on September 11, 2006, 12:25 pm
All,

Looking for advice on a home heating/cooling problem, here's the story:

We have a two story house (2100 sq ft, almost equally distributed up and
down) in central Texas (mild winters, somewhat hot summers). Lennox
single 4 ton HVAC unit roughly 7 years old, single zone system. Summers
aren't bad, although the upstairs rooms are a bit warmer than downstairs
- nothing too unpleasant. Although two rooms (that face south and are
over a two car garage) get pretty warm in the morning & afternoons.
Winters on the other hand are completely different. The downstairs is
consistently 10-15 degrees colder than upstairs. It's almost unusable
on colder (30's) nights. We've tried small space heaters downstairs,
but they really don't help much.

We've talked with several people about options and here are the leading
three:

* replace single pane windows with dual pane
* replace HVAC with a dual system, or more powerful (5 ton) with
continuous fan
* add damper system to current HVAC to create dual zone
system

The problem is all three solutions came from people who sell that
particular product, and all claim the same thing "this should solve 90%
of your problem". The first two are pretty expensive, so for that money
I expect more than a 90% solution. Also, I don't expect sales reps to
recommend a product they don't sell, so I'm not sure I'm get a straight
answer.

While money is a concern (I don't want to spend 50k to fix this) I am
willing to spend a reasonable amount if it solves the problem (3-15k).
We're going to stay in the house at least 10 years, but getting the
system to pay for itself in energy gains is not the leading priority.

We've looked at vinyl vs. Anderson Renewal windows and love the Anderson
windows, but the price is pretty steep and the sales rep was a bit odd.
Vinyl through Home Depot seems to have a great warranty (haven't read
the fine print), but it's still vinyl windows and I haven't been
convinced they're going to last - and it still just seems wrong to have
vinyl windows to me. They looked great until we saw Anderson windows.

A local company serviced our HVAC this year and when I asked the tech
his advice, he seemed to think a damper system (~3k) would significantly
help. We do have two returns (upstairs & downstairs), so adding a
thermostat downstairs (the one we have now us currently upstairs) sounds
good. He's the first person that's explained a damper system to me in a
way that he sounds like he knows what he's talking about.

So there you have it - I would really appreciate feedback from someone
(homeowner) who's done this and what the results were, or hearing from a
general contractor on recommendations.

thanks,
-andrew

twostoryhvac at gmail dot com

Posted by Goedjn on September 11, 2006, 1:09 pm

>All,
>
>Looking for advice on a home heating/cooling problem, here's the story:
>
>We have a two story house (2100 sq ft, almost equally distributed up and
>down) in central Texas (mild winters, somewhat hot summers). Lennox
>single 4 ton HVAC unit roughly 7 years old, single zone system. Summers
>aren't bad, although the upstairs rooms are a bit warmer than downstairs
>- nothing too unpleasant. Although two rooms (that face south and are
>over a two car garage) get pretty warm in the morning & afternoons.
>Winters on the other hand are completely different. The downstairs is
>consistently 10-15 degrees colder than upstairs. It's almost unusable
>on colder (30's) nights. We've tried small space heaters downstairs,
>but they really don't help much.
>

Putting a door at the top or bottom of the stairs to
restrict airflow will keep more of the heat on the ground floor,
and more of the cool on the top floor. After that,
it's just a matter of putting the heat or cold where it's
needed. If you can't block the between-floors
airflow, then you need some way to deliberately circulate
the air between floors, which should even out the temps.

Insulating and plugging leaks would reduce your
total climate-control load, but it's sounds like
balancing is your current issue.

Multi-zone systems are for when you want to
reduce the load further by NOT controlling
the temperature in unused spaces.



Posted by namesnotbob on September 11, 2006, 1:35 pm
A no cost method that you can try is close the registers on the second
story during the winter so that more air blows downstairs and less
upstairs.


Posted by RayV on September 11, 2006, 1:35 pm

Goedjn wrote:
> >All,
> >
> >Looking for advice on a home heating/cooling problem, here's the story:
> >
> >We have a two story house (2100 sq ft, almost equally distributed up and
> >down) in central Texas (mild winters, somewhat hot summers). Lennox
> >single 4 ton HVAC unit roughly 7 years old, single zone system. Summers
> >aren't bad, although the upstairs rooms are a bit warmer than downstairs
> >- nothing too unpleasant. Although two rooms (that face south and are
> >over a two car garage) get pretty warm in the morning & afternoons.
> >Winters on the other hand are completely different. The downstairs is
> >consistently 10-15 degrees colder than upstairs. It's almost unusable
> >on colder (30's) nights. We've tried small space heaters downstairs,
> >but they really don't help much.
> >
>
> Putting a door at the top or bottom of the stairs to
> restrict airflow will keep more of the heat on the ground floor,
> and more of the cool on the top floor. After that,
> it's just a matter of putting the heat or cold where it's
> needed. If you can't block the between-floors
> airflow, then you need some way to deliberately circulate
> the air between floors, which should even out the temps.
>
> Insulating and plugging leaks would reduce your
> total climate-control load, but it's sounds like
> balancing is your current issue.
>
> Multi-zone systems are for when you want to
> reduce the load further by NOT controlling
> the temperature in unused spaces.

I got a noticeable improvement by blocking off my downstairs *return*
vents. This forces the AC to pull the hotter upstairs air and cool it
off. Since you have two returns you could try this by covering the
downstairs return with cardboard. If it works then you make a more
attractive cover. I plan to block off my upstairs returns in the
winter to improve the heat circulation.

Caution: Some of the HVAC techs have posted about the possibility of
freezing your a-coil due to reduced airflow. This is supposedly not a
problem with blocking a return but it is my CYA notice.


Posted by Don Young on September 11, 2006, 11:23 pm

> All,
>
> Looking for advice on a home heating/cooling problem, here's the story:
>
> We have a two story house (2100 sq ft, almost equally distributed up and
> down) in central Texas (mild winters, somewhat hot summers). Lennox
> single 4 ton HVAC unit roughly 7 years old, single zone system. Summers
> aren't bad, although the upstairs rooms are a bit warmer than downstairs
> - nothing too unpleasant. Although two rooms (that face south and are
> over a two car garage) get pretty warm in the morning & afternoons.
> Winters on the other hand are completely different. The downstairs is
> consistently 10-15 degrees colder than upstairs. It's almost unusable
> on colder (30's) nights. We've tried small space heaters downstairs,
> but they really don't help much.
>
> We've talked with several people about options and here are the leading
> three:
>
> * replace single pane windows with dual pane
> * replace HVAC with a dual system, or more powerful (5 ton) with
> continuous fan
> * add damper system to current HVAC to create dual zone
> system
>
> The problem is all three solutions came from people who sell that
> particular product, and all claim the same thing "this should solve 90%
> of your problem". The first two are pretty expensive, so for that money
> I expect more than a 90% solution. Also, I don't expect sales reps to
> recommend a product they don't sell, so I'm not sure I'm get a straight
> answer.
>
> While money is a concern (I don't want to spend 50k to fix this) I am
> willing to spend a reasonable amount if it solves the problem (3-15k).
> We're going to stay in the house at least 10 years, but getting the
> system to pay for itself in energy gains is not the leading priority.
>
> We've looked at vinyl vs. Anderson Renewal windows and love the Anderson
> windows, but the price is pretty steep and the sales rep was a bit odd.
> Vinyl through Home Depot seems to have a great warranty (haven't read
> the fine print), but it's still vinyl windows and I haven't been
> convinced they're going to last - and it still just seems wrong to have
> vinyl windows to me. They looked great until we saw Anderson windows.
>
> A local company serviced our HVAC this year and when I asked the tech
> his advice, he seemed to think a damper system (~3k) would significantly
> help. We do have two returns (upstairs & downstairs), so adding a
> thermostat downstairs (the one we have now us currently upstairs) sounds
> good. He's the first person that's explained a damper system to me in a
> way that he sounds like he knows what he's talking about.
>
> So there you have it - I would really appreciate feedback from someone
> (homeowner) who's done this and what the results were, or hearing from a
> general contractor on recommendations.
>
> thanks,
> -andrew
>
> twostoryhvac at gmail dot com
A low cost experiment is to just run the circulating fan continiously. Be
careful about closing dampers or covering returns as you can wind up with
inadequate airflow thru the furnace and overheating. A good technician could
possibly improve the situation by re-balancing the airflow. Anything you can
do to reduce the downstairs heat loss would help some. The percentage of off
time for the furnace, if any, will give you some indication as to whether
the system has adequate capacity.

Don Young



Similar ThreadsPosted
story March 6, 2007, 6:46 am
a painting story December 7, 2005, 9:36 am
TV programme looking for your story. December 16, 2005, 7:02 am
Tell us your Renovation Story July 25, 2006, 4:18 pm
I want to hear your story October 16, 2006, 11:07 am
STORY OF SUCCESS... January 29, 2007, 8:17 am
A story, not a question May 14, 2007, 6:35 pm
. OT - heartwarming story December 22, 2007, 1:59 pm
OT. Some what a, CHRISTMAS STORY December 24, 2007, 10:58 am
Insulation 1 1/2 story March 14, 2008, 11:21 am

Contact Us | Privacy Policy

XML SitemapXML Sitemap