>>I have a Dunkirk oil burner. When we went to turn it on last night,
>> the heat worked fine in the sexond floor (we have two heating zone, two
>> thermostats), but nothing on the first floor. The first floor
>> thermostat is in fine working condition--I reset all the settings,
>> checked the wiring and put in new batteries. What could this be?
>>
>
> First, it is not the burner. That just heats water.
>
> Most likely, the circulator pump of the first floor zone is not working.
> The thermostat switches a relay that turns on the pump. You should be
> able to feel it running.
>
> If you have a single pump, it could be a defective zone valve.
Yes, could very well be the zone valve. Usually they have a lever on the
side of them that you can move down to open them manually. If you do this
and have heat then that's the problem.
>
>
|