proper installation of double GFI receptacles in one box

Home Repair - - If it ain't broken, don't fix it. Otherwise look here. 

Bookmark this page:  YahooMyWeb Yahoo!  Google Google  Windows Live Favorites Windows Live  del.icio.us del.icio.us  digg digg  Add to Netscape Netscape
Subject Author Date
proper installation of double GFI receptacles in one box gerrykuff 05-03-2008
If you were  Registered and logged in, you could reply and use other advanced thread options
Posted by on May 3, 2008, 4:47 am
I am doing a complete bathroom renovation. I wish to install two GFI
receptacles in a double box. The incomming wire is always hot and
goes no further than the box in question. As there is already one
existing GFI recptacle in place i can see how its wired. can i just
pigtale its white and the new ones white to the incomming white and
pigtale the current black and the new black to the incomming black
and common the grounds

Posted by peter on May 3, 2008, 5:30 am
>I am doing a complete bathroom renovation. I wish to install two GFI
> receptacles in a double box. The incomming wire is always hot and
> goes no further than the box in question. As there is already one
> existing GFI recptacle in place i can see how its wired. can i just
> pigtale its white and the new ones white to the incomming white and
> pigtale the current black and the new black to the incomming black
> and common the grounds

Why not install a regular (non GFI) duplex receptacle downstream of the
existing GFI?



Posted by John Grabowski on May 3, 2008, 6:46 am

>I am doing a complete bathroom renovation. I wish to install two GFI
> receptacles in a double box. The incomming wire is always hot and
> goes no further than the box in question. As there is already one
> existing GFI recptacle in place i can see how its wired. can i just
> pigtale its white and the new ones white to the incomming white and
> pigtale the current black and the new black to the incomming black
> and common the grounds



Yes or you can do as Peter suggested to save a little on the cost of an
additional GFI. Put your pigtail wires from the second receptacle into the
LOAD terminals on the first GFI. That will make the second receptacle GFI
protected. The current code calls for a separate 20 amp circuit for the
bathroom.


Posted by Colbyt on May 3, 2008, 6:00 pm

>
>>I am doing a complete bathroom renovation. I wish to install two GFI
>> receptacles in a double box. The incomming wire is always hot and
>> goes no further than the box in question. As there is already one
>> existing GFI recptacle in place i can see how its wired. can i just
>> pigtale its white and the new ones white to the incomming white and
>> pigtale the current black and the new black to the incomming black
>> and common the grounds
>
>
>
> Yes or you can do as Peter suggested to save a little on the cost of an
> additional GFI. Put your pigtail wires from the second receptacle into
> the LOAD terminals on the first GFI. That will make the second receptacle
> GFI protected. The current code calls for a separate 20 amp circuit for
> the bathroom.

This is excellent advice but you will need to use the decora style duplex so
that you can find a 2 gang cover to fit.


--
Colbyt
Please come visit www.househomerepair.com



Posted by RBM on May 4, 2008, 3:10 pm

>
>>
>>>I am doing a complete bathroom renovation. I wish to install two GFI
>>> receptacles in a double box. The incomming wire is always hot and
>>> goes no further than the box in question. As there is already one
>>> existing GFI recptacle in place i can see how its wired. can i just
>>> pigtale its white and the new ones white to the incomming white and
>>> pigtale the current black and the new black to the incomming black
>>> and common the grounds
>>
>>
>>
>> Yes or you can do as Peter suggested to save a little on the cost of an
>> additional GFI. Put your pigtail wires from the second receptacle into
>> the LOAD terminals on the first GFI. That will make the second
>> receptacle GFI protected. The current code calls for a separate 20 amp
>> circuit for the bathroom.
>
> This is excellent advice but you will need to use the decora style duplex
> so that you can find a 2 gang cover to fit.
>
>
> --
> Colbyt
> Please come visit www.househomerepair.com

They actually make two gang Decora/Duplex plates, although a two gang
Decora/Decora plate would look more attractive



Similar ThreadsPosted
Re: Proper Receptacles for 20 Amp Circuit June 28, 2005, 1:07 pm
Proper Receptacles for 20 Amp Circuit June 28, 2005, 12:01 am
proper window installation September 15, 2005, 1:34 pm
Proper GFCI installation January 9, 2007, 5:10 pm
Gutters--Proper installation question June 16, 2005, 11:17 pm
Proper Installation of Corrugated Pipe for Drainage Purposes August 20, 2006, 6:40 pm
Basement receptacles GFI ... what about broken receptacles to control lighting ? May 31, 2008, 6:05 pm
installing double-pane windows: double-sided tape separating from window or window-frame May 31, 2006, 10:56 am
Drywall & Receptacles June 1, 2007, 4:49 pm
Switch/Receptacles? August 21, 2007, 11:12 am

Contact Us | Privacy Policy

XML SitemapXML Sitemap