remove completely (?) air vent on steam riser michalis0 01-09-2007
If you were  Registered and logged in, you could reply and use other advanced thread options
Posted by on January 9, 2007, 7:09 pm


Hi,

there is an air vent on the stream riser pipe in my apt.
The vent usually goes bad and starts producing loud noises (like
banging
with a hammer). That I assume happens because the pressure on the
stream riser
pipe can be quite high at times.

I don't even know why the air vent was placed there on the first place.
There is just a whole drilled in the pipe and in this whole the vent is
screwed in.
I presume they placed the vent so that the stream rises faster.

Can I remove completely the vent and just place/screw a bolt
where the air vent was? I am hoping that would remove the loud banging
problems. Any suggestions?

TIA
michalis


PexSupply QuikTrak 468x60
Posted by Speedy Jim on January 9, 2007, 7:31 pm


michalis0@gmail.com wrote:

> Hi,
>
> there is an air vent on the stream riser pipe in my apt.
> The vent usually goes bad and starts producing loud noises (like
> banging
> with a hammer). That I assume happens because the pressure on the
> stream riser
> pipe can be quite high at times.
>
> I don't even know why the air vent was placed there on the first place.
> There is just a whole drilled in the pipe and in this whole the vent is
> screwed in.
> I presume they placed the vent so that the stream rises faster.
>
> Can I remove completely the vent and just place/screw a bolt
> where the air vent was? I am hoping that would remove the loud banging
> problems. Any suggestions?
>
> TIA
> michalis
>

LOL Yes, can do anything you like.
(The landlord may just have an opposing view.)

The owner probably found out that steam distribution
on start-up was a problem and the main vent was the fix.
They are usually designed in and not simply "tapped"
into a riser.

The vent will have a tapered pipe thread so you'll want to
get a pipe plug with that thread. Small vents are 1/8" size,
but it may be larger. And that's "trade" size, not the apparent size.

Good luck. You might want to read your lease first....

Jim

Posted by on January 10, 2007, 10:18 am


Hammering sounds are usually caused by a slug of water trapped in the
pipes being slammed around by incoming steam. Try making sure all of
your radiators and any piping you see has a pitch back towards the
boiler. Shimming up the ends of the radiators and making sure the
pipes don't sag where they have long lateral runs

.
michal...@gmail.com wrote:
> Hi,
>
> there is an air vent on the stream riser pipe in my apt.
> The vent usually goes bad and starts producing loud noises (like
> banging
> with a hammer). That I assume happens because the pressure on the
> stream riser
> pipe can be quite high at times.
>
> I don't even know why the air vent was placed there on the first place.
> There is just a whole drilled in the pipe and in this whole the vent is
> screwed in.
> I presume they placed the vent so that the stream rises faster.
>
> Can I remove completely the vent and just place/screw a bolt
> where the air vent was? I am hoping that would remove the loud banging
> problems. Any suggestions?
>
> TIA
> michalis


Similar ThreadsPosted
removing completely (?) air vent on steam riser January 10, 2007, 12:58 pm
Slate tile staircase. Riser over tread or tread over riser. October 10, 2006, 1:02 am
Steam radiator air vent help December 3, 2006, 11:43 am
air vent for steam cast iron radiatiors December 8, 2005, 11:58 pm
Steam vent radiator threads stripped April 2, 2007, 10:02 pm
can I remove this vent coming out of our roof? March 5, 2006, 9:57 am
remove chimney and vent furnace outside March 16, 2006, 4:48 pm
basement stairs riser question November 5, 2007, 7:49 am
size of pipe to shower riser? July 28, 2008, 10:24 pm
Re: size of pipe to shower riser? July 29, 2008, 12:15 pm

Contact Us | Privacy Policy

XML SitemapXML Sitemap